Table 7 charge mode specifications – PROLiNK IPS5000 User Manual
Page 16

- 14 -
Table 7 Charge Mode Specifications
MODEL IPS5000R
IPS5000L
Nominal Input Voltage
230Vac
Input Voltage Range
180V~ 270Vac(Normal range)
100V~ 270Vac(generator/wide range)
Nominal Output Voltage
According to the battery type
Nominal Charge Current
20A(95-175v,gen/wide,only),
35A(175-275v)@35A setting
20A(175v-275v)@20A setting)
10A(95-175v,gen/wide,only),
20A(175-275v)@20A setting
10A(175v-275v)@10A setting)
Battery initial voltage(sps setup)
>35Vdc >70Vdc
Charger Short Circuit Protection
Unit shutdown automatic
Over Charge Protection
Bat. V ≥60Vdc, Fault, Buzzer alarm Bat. V ≥120Vdc,Fault, Buzzer alarm
Charge Algorithm
Three stage:
Boost CC (constant current stage) → Boost CV (constant voltage
stage) → Float (constant voltage stage)
Battery Type Setting(±0.3v/bat)
Boost CC/CV
Float
Voltage(V) Voltage(V)
Battery Type
48 96 48 96
Flooded 58.4 116.8
53.6 108
AGM/Gel 56.4 112.8 54 108
Charger current (+/-10%)
NOTE: data definition=IPS5000L (IPS5000R)