Table 6 inverter mode specifications – PROLiNK IPS5000 User Manual
Page 15
![background image](/manuals/343831/15/background.png)
- 13 -
Table 6 Inverter Mode Specifications
MODEL IPS5000R IPS5000L
Output Voltage Waveform
Pure Sine Wave
Rated Output Power(VA)
5000
Power Factor
0.84
Nominal Output Voltage(V)
230Vac
Output Frequency(Hz)
50Hz / 60Hz ± 1Hz
Output Voltage Regulation
±10% rms
Nominal Efficiency
>90%
Over-Load Protection
fault after 5s@≥150% load,
fault after 10s@110%~150% load,
Surge rating
10000VA
Capable of starting electric motor
2.5HP
Output Short Circuit Protection
Current limit (Fault after 4 cycles max)
Bypass Breaker Size
40A
Nominal DC Input Voltage
48V 96V
Min DC start voltage
40V 80V
Low DC Alarm
42.0 ± 1.2Vdc
84.0± 2.4Vdc
Low DC Alarm Recovery
43.2 ± 1.2Vdc
86.4± 2.4Vdc
Low DC Shut-down
40.0±1.2Vdc 80.0±2.4Vdc
Low DC Shut-down Recovery
44.0±1.2Vdc 88.0±2.4Vdc
High DC Shut-down
60.0±1.2Vdc 120.0
±2.4Vdc
High DC Shut-down Recovery
58.0±1.2Vdc 116.0
±2.4Vdc
Power saver setting
0W (Set “OFF” at LCD)
10±5W enter 5+/-2w leave (Set “ON” at LCD)
Tare loss(nominal)
Saver OFF:<50w
Saver ON:<10w
DC component of AC output
<100mv
Half wave load detection
Yes(when unbalance current>35A)
Power Limitation
Note: Necessary condition for DC low recovery is: Line voltage must be available for charging.