Warning – Alliance Laundry Systems HF900 User Manual
Page 31
4
31
WARNING
The washer-extractor should be connected to an individual branch
circuit not shared with lighting or other equipment.
Electrical Specifications HF575, IHF575, IHF135, CHF135
575 liters / 135 pounds
Boiler Fed/Steam Heat
Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Recommended Circuit
Breaker (US-market)
AWG/mm2
kW Standard
Heating Elements
Full Load
Amps
Recommended
Circuit Breaker
AWG/mm2
US NON-US
US NON-US
N
440-480 50/60
3
3+PE
27
30
32
10/6.0
9x4 kW
79
N/A
80
4/25
P
380-415 50/60
3
3+N+PE 27
30
32
10/6.0
79
N/A
80
4/25
Q
200-240 50/60
3
3+PE
52
60
60
8/10.0
9x3 kW
120 N/A
125
2/40
X
200-240 50/60
1/3
2/3+PE N/A N/A
N/A
N/A
N/A N/A
N/A
N/A
Alternative Electric Heat Options
N
440-480 50/60
3
3+PE
9x3 kW
66
N/A
70
4/25
P
380-415 50/60
3
3+N+PE
66
N/A
70
4/25
Q
200-240 50/60
3
3+PE
79
N/A
80
4/25
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
Table 3