MCB - Ten Position Dipswitch:
Dipswitch configurations are READ ONLY ON POWER UP. These switches are only to be set at the factory or by authorized trained
personnel! Once set the boiler will operate according to the chosen options. If a switch is changed, power must be cycled before the
change will take effect. The status of all dipswitches can be observed on the system status screen on the UIM.

MCB/FCB Dipswitches:

Dipswitch Function

Switch Position

Hot Water Boilers

Hydronic Heating Boiler

Switch 1: Selection of the type of boiler application:

On = VW

Off = VB

Switch 2: Trials for ignition:

On = 3

Off = 1

Switch 3: IRI Gas Valve Not Available:

Switch 4: Controlling Probe:

On = Tank (Remote)

Off = Inlet

Switch 5: Powered Venter:

On = Yes

Off = No

Switch 6: Low Water Cut Off: (LWCO)

On = Yes

Off = No

Switch 7: Low Gas Pressure

On = Yes

Off = No

Switch 8: Modulation:

On

NOTE: If the unit powers up with the number of stages selected by dip switches exceeding the number of FCBs, the MCB will detect this
condition and go into a hard lockout. After changing the dipswitches, the power must be cycled off and back on to accept any
changes.

Example of Dipswitch configuration:
VB model, 1ignition trial, not used, tank / remote probe, no power vent, No LWCO,
no low gas pressure, modulation, not used, not used.

MCB - Three position Dipswitch:
This dipswitch is similar to the FCB dipswitches described below, but with only three switches being used: the number of blower speeds
(switch #3), Hi Gas option (switch #2) and a spare (switch #1). Only the blower speed and Hi Gas options are the required selection,
within the MCB, see Figure 17.

Dipswitch Function:

Dipswitch Position

Switch 1: Spare:

Switch 2: Hi Gas pressure switch:

On = Yes

Off =

No

Switch 3: Number of Blower Speeds:

On = 1 speed,

Off =

2 speed

Example of Dipswitch configuration:
No High Gas, 1 blower speed.