When installing the tube heater system, clearances to combustibles for the model tube heater and
configuration must be maintained . Refer to Chart 1 .1 below to determine the required distances for your model .

5

MP

Series

Model Number

Mounting

Angle*

Sides

Front

Behind

Top

Below

MP-(25,30,40)-80[N,P]

14

14

6

66

45°

39

8

10

66

with 1 side shield

29

8

6

66

with 2 side shields

16

16

6

66

20 ft . from burner

7

7

6

30

MP-(30,40,50)-115[N,P]

20

20

6

76

45°

58

8

10

76

with 1 side shield

42

8

6

76

with 2 side shields

20

20

6

76

20 ft . from burner

7

7

6

30

MP-(40,50,60)-150[N,P]

24

24

6

83

45°

58

8

10

83

with 1 side shield

42

8

6

83

with 2 side shields

23

23

6

83

20 ft . from burner

11

11

6

46

MP-(50,60,70)-200[N,P]

41

41

6

100

45°

63

8

10

100

with 1 side shield

54

8

6

100

with 2 side shields

30

30

6

100

20 ft . from burner

11

11

6

50

1.0

Safety • Clearance to Combustibles

Chart 1.1 •

Clearance to Combustibles in Inches (See Figure 1 .1 for Mounting Angles)

Figure 1.1

Mounting Angles

0° Mounting Angle

45° Mounting Angle

0° Mounting Angle

with 1 Side Shield

(P/N: SSE)

0° Mounting Angle

with 2 Side Shields

(P/N: SSE)

Side

Side

Below

Top

Front

Behind

Below

Top

Front

Behind

Below

Top

Side

Side

Below

Top

The minimum end clearance for all models is 12 inches .
* Maximum mounting angle is 45° . Heaters mounted on an angle between 0° to 45° must maintain

clearances posted for 0° or 45°; whichever is greater .

The stated clearance to combustibles represents a surface temperature of 90°F (32°C) above room
temperature . Building materials with a low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply,
etc .) may be subject to degradation at lower temperatures . It is the installer’s responsibility to assure that
adjacent materials are protected from degradation .