MP

Series

Standard Configuration: From the factory, the heater is configured as follows:

1

’Master’ Heater:

ON

2

Outdoor Air Probe:

OFF

3

Premium User Interface:

ON

4

Potentiometer:

OFF

5

Thermostat:

OFF

6

Economy Mode:

OFF

7

Standard Mode:

ON

8

Comfort Mode:

OFF

Figure 2.7

Standard Configuration of DIP Switches

*If outdoor air sensor is equipped, switch DIP#2 to the ON position .
Use Diagram “A” on Page 8 for connecting the Premium User Interface to the heater .

‘Address’ DIP Switches

The Address DIP Switches are only utilized in a ‘Master/Slave’ installation or for BMS configurations . All
other configurations ignore the settings of these switches . When addressing a heater for a ‘Master/Slave’
configuration, the ‘Slave’ heaters must be addressed for proper operation . Each ‘Slave’ must have its own
unique configuration, determined by the installer . Up to 256 unique combinations can be configured .

Setting the ‘Slave’ Heater(s): The ‘Slave’ heater configuration is set by selecting the ‘Slave’ position on
switch #1 in the “Options” DIP Switches . The address switches become active when the ‘Slave’
configuration is selected . On the Address DIP Switches, configure each heater so that each heater has its
own unique configuration . An example is provided below for a three heater zone system .

Figure 2.8

Example of three DIP Switches

ON

8
7
6
5
4
3
2
1

ON

8
7
6
5
4
3
2
1

MASTER

OA SENSOR*

USER INTERFACE

POTENTIOMETER

EXT. THERMOSTAT

ECONOMY

STANDARD

COMFORT

ON

8
7
6
5
4
3
2
1

ON

8
7
6
5
4
3
2
1

MASTER

OA SENSOR*

USER INTERFACE

POTENTIOMETER

EXT. THERMOSTAT

ECONOMY

STANDARD

COMFORT

ON

8
7
6
5
4
3
2
1

ON

8
7
6
5
4
3
2
1

MASTER

OA SENSOR*

USER INTERFACE

POTENTIOMETER

EXT. THERMOSTAT

ECONOMY

STANDARD

COMFORT

Master Heater Slave Heater

Slave Heater

2.0

Installation • Configuring the Heater

Master Heater

(Factory Default)

Slave Heater

(One Address Configuration)

Slave Heater

(Different Configuration)

MASTER DIP SETTINGS

LEGEND

SLAVE DIP SETTINGS

FOR USE WITH TP-3228

NOTE: SHIELD GROUND MUST BE TIED TO GROUND, AS SHOWN

MASTER HEATER

SLAVE HEATER

PREMIUM

USER

INTERFACE

+15V

485-

485+

GND

CHASIS GND

485-

485+

GND

+15V

485-

485+

GND

CHASIS GND

485-

485+

GND

BK