MaxPower Corp OceanAire Portable User Manual
Page 22

PROBLEM: WATER LEAKING FROM PAN
1. (CAUSE) Leaky drain pan
(REMEDY) Locate leak and repair pan.
2. (CAUSE) Loose evaporator, drain or condensate pump hose
(REMEDY) Tighten connections.
3. (CAUSE) Defective condensate pump or excessive lift on pump
(REMEDY) Examine to see if elevation exceeds 20 ft. (if it does, a larger pump will be required).
Otherwise, change pump if defective. Pump will operate properly against 20 ft. of water total head pressure
on pump. If combination of vertical height and horizontal drain line exceeds 20 ft. of water pressure drop,
problems will occur.
PROBLEM: THERMOSTAT (LCD) LIQUID CRYSTAL DISPLAY WINDOW DOES NOT
ILLUMINATE.
1. (CAUSE) No Power or defective thermostat.
(REMEDY) Make sure 24 volts are present at the thermostat terminals.
PREVENTIVE MAINTENANCE
AirBoss Series air conditioners are designed to last a long time and to give maximum performance and
reliability with minimum maintenance. To prolong the life of the unit, regular maintenance must be
performed as specified below:
1. BLOWER MOTORS
The motors on all units have permanently lubricated bearings. No oiling is necessary
20
airbossmanpg20
Evaporator Blower Assembly
Condenser Blower Assembly
Evaporator Coil
Condenser Coil