CHAPTER 5-Calibration


Calibration

 Navigate to the scale factor on all displays and set to 1.0000. Exit programming mode.

 Reset all counters.

 Using a container, dispense material. If volume is to be used the container must have volumetric

marks on it.

 Once the container has been filled, record what the display reading is.

 Using the net weight or volume from the container divide it by the monitor display.

 This will be the adjusted scale factor that needs to be entered into all of the displays.


Example:
Dispensed material is 12.50 lbs. Monitor displayed weight is 8.56 lbs.

12.50/8.56= 1.46


 1.460 should be entered into the scale factor for each monitor. Once this is done the display will

read the correct weight once you exit out of program mode.

 Verify by resetting all counters and dispensing into bucket and checking vs. the displayed value.

 If the reading has a large variance, repeat the above steps. If the variance is small, manipulate

the scale factor until the display is correct.