Magnum Venus Plastech CB-8000-xxx Resin Monitor User Manual
Page 17
INSTALLATION AND OPERATIONS MANUAL
CB-8000-XXX
MAGNUM VENUS PLASTECH
REV 1.05
APRIL 2013
PAGE 17
CUB5 display (small display)
Using the SEL and RST keys on the front of the display you will need to navigate to the correct module for
programming. Module 1-INPUT (inputs) is the only one that needs to be modified.
Once you have entered the module for programming use the following chart to navigate the module. The
greyed out parameters are not available.
The following is a step by step procedure on how to change the relevant settings. The only two settings that need
to be changed are the decimal point and the scale factor. All other settings are to remain at default.
Note: The small display should never have an R on the left hand side. This means that it is set for rate
reading. Pushing the
SEL key will toggle from rate to count.
Press and hold the SEL key until meter enters program mode.
Display will read
INPUt
Press the RST key.
Display will read
INPUT A-b
Press the SEL key.
COUNT MODE
Display will read
INP Ab
. Default setting
should be
Cnt ud.
Press the SEL key.
COUNTER A DECIMAL POINT***
Display will read
CntA dP
Decimal point setup.
At this point you will have the option to set
the decimal point. Press the RST key if you
wish to set the decimal point.