2-WIre standard

The 2-wire Standard configuration translates the output signal from the turbine flowmeter’s pickup coil into a current

value. The 2-wire Standard configuration produces an output signal using a resistor to convert the electrical current

variations into voltages. In this configuration, the power supply travels on the signal wire. 2-wire connections are

effective transmitting the signal over long distances.

To connect the SP714-S2i for 2-wire Standard:

1. Remove the SP714-S2i housing cover.
2. Pull the SP714-S2i board from the housing for access to the TB1 terminal block and the S1 switches.
3. Attach proper cable glands and/or conduit connectors to the SP714-S2i, the pulse acquisition device, and DC power supply.
4. Run the wires (through proper conduit) between the SP714-S2i, the pulse acquisition device, and DC power supply.
5. Set the first S1 switch to the

ON position and the second S1

switch to the OFF position.

6. Splice the resistor onto the +V

leg from the DC power supply.

The value of the resistor can be

determined using the information below.

7. Wire the SP714-S2i to the pulse

acquisition device and DC

power supply as indicated in the

schematic.

8. If necessary, adjust the input

signal sensitivity (R1), activate

the diagnostic test oscsillator

(SW2), and/or check the

diagnostic operational LEDs (D1

& D2). See page 11.

9. Coil the wires underneath the

CPU board and place the board

inside the housing, ensuring

the wires are not pinched, and

replace the housing cover.

2-WIre standard WIrInG

S1

ON

ON

1 2

GND

1

Signal

+V

0V

Signal Ground

Cable Shield

Resistor (R

P

)

Two

Conductor

Shielded

Cable

Position 1 - ON

Position 2 - OFF

ON

ON

1 2

Electronic Register

or

Flow Computer

Z

input resistance

DC Power

Supply

Chassis GND

S1

TB1

INTERNAL OPERATING PRINCIPLE

3 2 1

2 1

TB2

Pickup Coil Signal

TB1

3 2 1

Connect Chassis GNDs at pulse acquisition device only

If the total system resistance in a 2-wire standard

configuration exceeds the recommended value, the

preamplifier may function irregularly as a result of

insufficient supply voltage to the terminals.

!

cautIon !

sP714-s2i connections

Pulse Acquisition Device

Signal

Signal Ground

Sponsler IT 400

TB2 (1)

TB2 (2)

LectroCount
LCR-II/LCR 600

J8 (33)

J8 (37)

Toptech MultiLoad

TB2B (V+ any)

TB2B (V COM any)

Maximum Cable Length: 380 m (1200’)
Minimum Wire Gauge: 0.75 mm

2

(18 AWG)

Maximum cable wire resistance must be less than

30 Ω

R

cable

= R

w

1

+ R

w

2

(both wires in cable)

Total system resistance with +24 VDC power supply must be between

250

and

400 Ω

R

system

= R

cable

+ R

P

Maximum System Current

I

max

=

90

m

A

I

max

=

Resistor (

R

P

) Power Dissipation

P

Rd

=

Resistor Value - 2-wire Standard

(V

dc

)

2

Rp

V

dc

R

system

24 VDC Power Supply: R

p

= 330 Ω, 2 W

12 VDC Power Supply: R

p

= 150 Ω, 2 W

Recommended Resistor Value (R

p

)

8