Wiring Specifi cations

Refer to the following steps for details on power and
accessory wiring for the operator.

AC Power Wiring

1. Find the listing on this page corresponding to the model, voltage and

horsepower rating of your operator.

2. The distance shown in the table is measured in feet from the

operator to the power source. DO NOT EXCEED THE MAXIMUM
DISTANCE.
These calculations have been based on standard 115 V
and 230 V supplies with a 10% drop allowable. If your supply is under
the standard rating, the runs listed may be longer than what your
application will handle, and you should not run wire too near the
maximum distance for the gauge of wire you are using.

3. When large-gauge wire is used, a separate junction box (not

supplied) may be needed for the operator power connection.

4. Wire length calculations are based on the National Electrical Code,

Article 430 and have been carefully determined based on motor
inrush, brake solenoids, and operator requirements.

5. Connect power in accordance with local codes. The green ground

wire must be properly connected.

6. Wire insulation must be suitable to the application.

7. Electrical outlets are supplied in all 115 VAC models for convenience

with occasional use or low power consumption devices only. If
you choose to run dedicated equipment from these devices, it will
decrease the distance for maximum length and the charts will no
longer be accurate.

DC Control and Accessory Wiring

1. All control devices are now 24 VDC, which can be run up to 2000

feet with 14 AWG wire.

2. Control wiring must be run in a separate conduit from power wiring.

Running them together may cause interference and faulty signals in
some accessories.

3. A three-wire shielded conductor cable is required to connect two

operators together for dual operation. You must use Belden 8760
Twisted Pair Shielded Cable (or equivalent) only – P/N 2500-1982,
per foot). See Page 19 for details of this connection. Note: The shield
wire should be connected in both the operators.

WARNING

ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE AND
THE OPERATOR MUST BE MADE BY A LICENSED ELECTRICIAN
AND MUST OBSERVE ALL NATIONAL AND LOCAL ELECTRICAL
CODES.

USE COPPER WIRE ONLY!

MODEL SG POWER WIRING

VOLTS & HP

MAXIMUM DISTANCE (FEET)

WIRE GAUGE

SINGLE

DUAL

115 VOLTS

1/2-HP

222

111

12

354

177

10

566

283

8

900

450

6

230 VOLTS

1/2-HP

894

447

12

1422

711

10

2264

1132

8

3600

1800

6

MODEL SG-D POWER WIRING

VOLTS & HP

MAXIMUM DISTANCE (FEET)

WIRE GAUGE

SINGLE

DUAL

115 VOLTS

1/2-HP

222

111

12

354

177

10

566

283

8

900

450

6