Electrical connection, Operators must be properly grounded, 120 volt electrical plug – Controlled Products Systems Group AOMSL1501HPDC User Manual
Page 12: For power wire enclosure use ul listed conduits, Power switch

11
2
3
0
V
2
3
0
V
1
1
5
V
1
1
5
V
GRD LINE 1 LINE 2
All gate operators
be properly grounded.
A proper ground in a gate operator installation minimizes or prevents damage from an electrical charge, such as a near
lightning strike or an electrical static discharge.
.
Use a single wire for the ground.
DO NOT splice two wires for the ground. If the wire breaks or is cut, replace it with a
single length.
NEVER use two wires for the ground.
Check with your City code for proper earth ground rod type and proper grounding procedures.
MUST
ELECTRICAL CONNECTION
120 Volt
Electrical
Plug.
Power connection | 115VAC | 220VAC Single Phase
LINE 1 = 115V HOT 220V LINE 1
LINE 2 = 115V N 220V LINE 2
Connect to ground. Use a proper
ground rod for a
ground reference.
Use the shortest and thickest wire possible for ground.
GND
For power wire enclosure
use UL listed conduits.
OPERATORS
MUST BE PROPERLY GROUNDED!
Power switch
For power, a minimum of a
dedicated circuit
breaker is needed.
20-Amp
NOTE:
When applying 230V to
operator make sure voltage
switch is flipped to 230V
position.
NOTE: To use the 120VAC
accessory outlet, connect white
wire from the outlet to neutral.
Only when using 120VAC as the
power source.