3 wiring plan, single chamber housing – Burkert Type 8112 User Manual
Page 18
5
Open the terminals with a screwdriver
6
Insert the wire ends into the open terminals according to the wiring
plan
7
Tighten the terminals with a screwdriver
8
Check the hold of the wires in the terminals by lightly pulling on
them
9
Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
10 Screw the housing cover back on
The electrical connection is finished.
5
.3 Wiring plan, single chamber housing
N
N A M U R
( I E C 6 0 9 4 7 - 5 - 6 )
m a x .
m i n .
S i m u l .
+
-
0,5 g / cm3
0,7 g / cm3
3
6
5
7
1
2
4
Fig. 10: Electronics and connection compartment, single chamber housing
1
Control lamp
2
DIL switch for characteristics reversal
3
DIL switch for sensitivity adjustment
4
Ground terminal
5
EMC filter element
6
Simulation key
7
Connection terminals
For connection of the amplifier according to NAMUR (IEC 60947-5-6,
EN
50227). You can find further information in the "Technical data".
Electronics and connec-
tion compartment
Wiring plan
18
LEVEL SWITCH
8112 • with NAMUR output
5 Connecting to power supply
32052
-EN
-120418