95
88
88
180
91
21
75
114
105
104
Fig. 4: Dimensions in mm of the SE35 electronic module
Table 2: Height H in mm of SE35 electronic module associated to
an S030 fitting-sensor
DN (mm)
06
08
15
20
25
32
40
50
65
H (mm)
134 134 139 137 137 140 144 151 151
H
1)
The height H does not
depend on the type of con-
nection or on the material.
6.3.2. General data
Type
8025
8035
Pipe diameter
DN20 (except for DN specified
p.13) to DN400
DN6 to
DN65
Type of fitting
S020
S030
Fluid temperature
The fluid temperature may be restricted by the
fluid pressure and by the material of the fitting
used. See Fig. 5 et Fig. 6
Fluid pressure
The fluid pressure may be restricted by the fluid
temperature and by the material of the fitting
used. See Fig. 5 et Fig. 6
Flow rate measurement
• Measurement range
• Measurement error
with a teach-in
procedure (teach-in
function)
• Measurement error
with K factor of fitting
used
• Linearity
• Repeatability
• 0,2 to 10 m/s
• ±0,5 % of the full scale
• ± (0,5% of the full scale + 2,5 % of the
measured value) 1)
• ±0,5 % of the full scale 1)
• ±0,4 % of the measured value
Power supply
2 batteries of 9 V (6LR61)
Minimum autonomy: 1 year at 20° C
1)
Determined in the following reference conditions: fluid = water,
water and ambient temperatures = 20 °C, upstream and down-
stream distances respected, appropriate pipe dimensions.