beautypg.com

Burkert Type 8056 User Manual

Page 30

background image

SE56

30

MENU 6 - OUTPUTS

(POS. 6.1-4) Function corresponding to on/off output 1-2-3-4

[OUT1=XXXXXX]

Choice of the function corresponding to digital Output 1. The functions are listed in the table below:

(POS. 6.5) Function and the range of current output n.1

[OUT.mA1=X÷XX+]

Choice of the function and the range of current output N.1. There are three fields to modify:

‰

Scale zero: 4 or 0 mA; Full scale: 20 or 22 mA

‰

Field: + = positive, - = negative, blank = both, -0+ = central zero scale

The values corresponding to the scale points are shown in the following chart:

In hardware alarm conditions “HW ALARM” (interrupted coils, empty pipe, measure error) the current
value is configured by the function “mA v. fault” (pos. 4.6) and it is expressed as percentage of a
fixed current range, where: 0% = 0mA e 110% = 22mA.

CURRENT VALUES IN mA ASSOCIATE TO THE % VALUE OF FULL SCALE

POSSIBLE FIELD

REVERSE FLOW VALUE

ZERO

DIRECT FLOW VALUE

d -110%

-100% 0%

+100%

t+110%

OutmA = 0 ÷ 20 +

0

0

0

20

20

OutmA = 0 ÷ 22 +

0

0

0

20

22

OutmA = 4 ÷ 20 +

4

4

4

20

20

* OutmA = 4 ÷ 22 +

4

4

4

20

22

OutmA = 0 ÷ 20 -

20

20

0

0

0

OutmA = 0 ÷ 22 -

22

20

0

0

0

OutmA = 4 ÷ 20 -

20

20

4

4

4

OutmA = 4 ÷ 22 -

22

20

4

4

4

OutmA = 0 ÷ 20

20

20

0

20

20

OutmA = 0 ÷ 22

22

20

0

20

22

OutmA = 4 ÷ 20

20

20

4

20

20

OutmA = 4 ÷ 22

22

20

4

20

22

OutmA = 0 ÷ 20 –0+

0

0

10

20

20

OutmA = 0 ÷ 22 –0+

0

1

11

21

22

** OutmA = 4 ÷ 20 –0+

4

4

12

20

20

OutmA = 4 ÷ 22 –0+

4

4.8

12.8

20.8

22

22 mA

20 mA

-110% F.S.

-100% F.S.

+100% F.S. +110% F.S.

zero

4 mA

I (mA)

I (mA)

20 mA

-110% F.S.

-100% F.S.

+100% F.S. +110% F.S.

zero

12 mA

4 mA

FUNCTIONS FOR OUTPUTS 1, 2, 3, 4

OFF: DISABLED
PLS+: PULSE FOR POSITIVE FLOW RATE (ONLY OUTPUT 1-2)
PLS-: PULSE FOR NEGATIVE FLOW RATE (ONLY OUTPUT 1-2)
PLS: PULSE FOR POSITIVE AND NEGATIVE FLOW RATE (ONLY OUTPUT 1-2)
SIGN: FLOW DIRECTION OUTPUT (ENERGIZED = -)
RANGE: RANGE INDICATION OUTPUT (ENERGIZED = SCALE 2)
MAX AL+: MAX DIRECT FLOW RATE OUTPUT(ENERGIZED = AL. OFF)
MAX AL-: MAX REVERSE FLOW RATE OUTPUT(ENERGIZED = AL. OFF)
MAX AL: MAX DIRECT/REVERSE FLOW RATE OUTPUT(ENERGIZED = AL. OFF)
MIN AL+: MIN DIRECT FLOW RATE OUTPUT(ENERGIZED = AL. OFF)
MIN AL-: MIN REVERSE FLOW RATE OUTPUT(ENERGIZED = AL. OFF)
MIN AL: MIN DIRECT/REVERSE FLOW RATE OUTPUT(ENERGIZED = AL. OFF)
MAX+MIN±: MAX AND MIN FLOW RATE ALARM OUTPUT (ENERGIZED = AL. OFF)
P.EMPTY: EMPTY PIPE ALARM OUTPUT (ENERGIZED = FULL PIPE)
OVERFLOW.: OUT OF RANGE ALARM OUTPUT (ENERGIZED = FLOW RATE OK)
HARDW AL.: CUMULATIVE ALARM OUTPUT interrupt coils, empty pipe, measure error (ENERGIZED = NO ALARMS
EXT. COMM.: ONLY AVAILABLE WITH DATA LOGGER MODULE
BATCH AL: BATCH ALARM
BATCH SYN.: AT THE AND OF BATCH THE OUTPUT CHANGE STATUS
END BATCH.: END BATCH OUTPUT (ENERGIZED =BATCH IN PROGRESS)
PREBATCH.: PREBATCH OUTPUT (ENERGIZED = PREBATCH IN PROGRESS)

* Example 1: out 4÷22 +

** Example 2: out 4ч20 –0+

This manual is related to the following products: