OPERATION STAGE ON INPUT 1 and 2 or 1 and 3 (BATCH FUNCTION)
Start batch via input 1 stop from output selection
formula 00 or 01 via input 2
Block totalizer via input 1, start batch via
input 2
Block and reset totalizer via input 1 start batch
via input 2 consent mode to batch enable
Necessary conditions for enable the function
x
POS. 5.8 ENABLED
x
POS. 6.1 or 6.3 on END BATCH
x
POS. 5.8 or/and 5.9 on BM SELECT
The signal block for the totalizer always 
interrupts the batch. Exciting again the 
input 2 or 3 is been able to get 2 
results: 
1) T< 1Sec = restart interrupted 
 batch 
2) T between 1 and 4 Sec = reset 
 interrupted batch. Note: will be 
 necessary give a new impulse 
 of start to the input 2 (T< 1Sec) 
 to begin a new batch
Necessary conditions for enable the
function
x
POS. 5.4 (Count lock) ENABLE
x
POS. 6.1 or 6.3 on END BATCH
x
POS. 5.8 or 5.9 on BATCH
x
POS. 5.2 (T2) ENABLE
The signal block for the totalize always stops 
the batch. With the function of reset T2 enable 
on descent front of input 1 comes reset the 
totalize of the batch in course. Therefore the 
presence of the consent or a new pulse on the 
input 2 or 3 they will determine the start of a 
new batch
Necessary conditions for enable the function
x
POS. 5.4 (Count lock) ENABLE
x
POS. 5.8 or 5.9 on BATCH
x
POS. 9.7 (consent mode) ENABLE
x
POS. 5.2 (T2) ENABLE
3-40 V
0-1.5 V
Start
Opening 
valve
Closing
valve
Opening
valve
Closing
valve
BATCH FORMULA 00
BATCH FORMULA 01
BATCH FORMULA 00
BATCH FORMULA 01
3-40 V
INPU
T 2
OUT
PUT
INPU
T 1
3-40 V
0-1.5 V
Start
Start
Opening 
valve
Closing
valve
Opening
valve
Closing
valve
NEW BATCH
RESTART INTERRUPTED
BATCH
OUT
PUT
OUT
PUT
INPU
T 2
INPU
T 2
INPU
T 1
T
<1 Sec.
T
co
mp
reso
t
ra 1 e 4 Sec.
3-40 V
0-1.5 V
Start
RESET
T<1 Sec.
Start
Opening 
valve
Closing
valve
Opening
valve
Closing
valve
INTERRUPTED BATCH
0-1.5 V
3-40 V
BLOCK
0-1.5 V
3-40 V
Start
INPU
T 2
Opening 
valve
Closing
valve
Opening
valve
Closing
valve
0-1.5 V
3-40 V
BLOCK RESET
T2
INPU
T 1
OUT
PUT
INTERRUPTED BATCH
NEW BATCH
INTERRUPTED BATCH