Type 8660 control center, 4 dip-switch – Burkert Type 8660 User Manual
Page 12
Type 8660 Control Center
________________________________________________________
- 12 -
5.4 DIP-switch
(only for Control Center 2 and 3)
DIP-switch 1: Presettings for the passenger area roof unit
(passenger area blower or roof blower)
Setting on:
passenger area blower will be automatically switched on when
the motor is switched on, and when the motor is switched off, the
blower will also switch off. The blowers can additionally be
switched on and off with the appropriate key.
Setting off:
passenger area blower will not be automatically switched on.
DIP-switch 2: Presettings for the blower level 1
Setting on:
front box blower level 1 will, in Ignition off, be switched on by the
time-switch 20 min. after the supplementary heater is switched on,
and switched off again after a further 20 min.
Setting off:
front box blower level 1 will not be automatically switched on.
The location of the two DIP-switches in the Control Center can be seen in Figure 3.
The DIP-switches must be set before connecting to the power supply.