Electrical connections, Devicenet field bus module technical data, Overview – Burkert Type 8645 User Manual
Page 7
24
GB
Electrical connections
Voltage supply
M12, plug 4-pin, max. 4 A
CANopen incoming
M12, plug 5-pin, a-coded
CANopen outgoing
M12, jack 5-pin, a-coded
RIO M8,
jack
Address setting
via rotary encoder switch
Address range
0 to 99
Integrated diagnostic
3-pin, (RM 2.54)
LEDs
2 x bus status
2 x fault indication
3 x supply voltage
Connection table
PI
N BUS IN /
BUS OUT
Power / Supply Voltage
RIO
1
Screen
4)
+24 V Output (U
o
)
CAN-H
2
CAN_V+(n.c.) +24 V Logic / Sensors (U
i
) CAN_L
3
GND
GND Logic / Sensors (U
i
)
Screen
4)
4
CANHigh
GND Output (U
o
)
n.c.
5
CANLow
-
-
4)
The screen terminal is connected to the FE contact.
25
GB
DEVICENET FIELD BUS MODULE
Technical Data
Operating voltage
24 V; -15 % / +20 %
Residual ripple
2 V
ss
Current consumption
Inputs / Logic
max. 1 A
Outputs
max. 4 A (M12)
DeviceNet
Transmission rate
adjustable via rotary encoder
switch
Rate [kBaud]
0
125
1
250
2
500
Overview
Detail drawing
Diagnostic / status LEDs (20)
BUS Status
U
i
logic voltage
F
S
Error
select
U
O
output voltage
F
N
Error
number
U
S
sensor voltage
26
GB
8
9
16
14
18
15
19
13
17
21
20
25
23
22
26
24
54
8
FE contact
9
FE contact
13 Type plate
14 Label panel
BUS IN
15 Connection BUS IN
(M12-b)
16 Label panel
BUS OUT
17 Connection BUS OUT
(M12-a)
18 Rotary encoder switch (x1)
19 Rotary encoder switch
(x10)
20 Diagnostic / status LEDs
(see detail drawing)
21 DIN rail mounting
22 Label panel Power
23 Connection Power
24 Label panel RIO
25 Connection RIO (M8)
26 Diagnostic and update
interface
54 Rotary encoder switch
baud rate
27
GB
Electrical Connections
Voltage supply
M12, plug 4-pin, max. 4 A
DeviceNet incoming
M12, plug 5-pin, a-coded
DeviceNet outgoing
M12, jack 5-pin, a-coded
RIO M8,
jack
Address setting
via rotary encoder switch
Address range
0 to 63
Integrated diagnostic
interface
3-pin, (RM 2.54)
Diagnostic LEDs
2 x bus status
2 x fault indication
3 x supply voltage
Connection table
PI
N BUS IN /
BUS OUT
Power / Supply Voltage
RIO
1 Screen
4)
+24 V Output (U
o
)
CAN-H
2 n.c.
+24 V Logic / Sensors (U
i
)
CAN_L
3 GND
GND Logic / Sensors (U
i
)
Screen
4)
4 CANHigh
GND outlet (U
o
)
n.c.
5 CANLow
-
-
4)
The screen terminal is connected to the FE contact.