Electrical connections, Canopen field bus module technical data, Overview – Burkert Type 8645 User Manual
Page 6
20
GB
8
FE contact
9
FE contact
13 Type plate
14 Label panel BUS IN
15 Connection BUS IN
(M12-b)
16 Label panel
BUS OUT
17 Connection BUS OUT
(M12-b)
18 Rotary encoder
switch (x1)
19 Rotary encoder
switch (x10)
20 Diagnostic / Status LEDs
(see detail drawing)
21 DIN rail mounting
22 Label panel Power
23 Connection Power
24 Label panel RIO
25 Connection RIO (M8)
26 Diagnose and update
interface
21
GB
Electrical connections
Voltage supply
M12, plug 4-pin, max. 4 A
Profi bus incoming
M12, plug 5-pin, b-coded
Profi bus outgoing
M12, jack 5-pin, b-coded
RIO M8,
jack
Address setting
via rotary encoder switch
Address range
0 to 99
Integrated diagnostic
interface
3-pin, (RM 2.54)
Diagnostic LEDs
2 x bus status
2 x fault indication
3 x supply voltage
Connection table
PIN
BUS IN /
BUS OUT
Power / Supply Voltage
RIO
1
5 V
+24 V Output (U
o
)
CAN-H
2
A signal
+24 V Logic / Sensors (U
i
) CAN_L
3
GND
GND Logic / Sensors (U
i
)
FE
4
B signal
GND Output (U
o
)
n.c.
5
FE
-
-
22
GB
CANOPEN FIELD BUS MODULE
Technical Data
Operating voltage
24 V; -15% / +20%
Residual ripple
2 V
ss
Power consumption
Inputs / Logic
max. 1 A
Outputs
max. 4 A (M12)
CANopen
Transmission rate
adjustable via rotary encoder
switch
Rate [kBd]
Rate [kBd]
0 1000
4
125
1 800
5
100
2 500
6
50
3 250
7
20
Overview
Detail drawing
Diagnostic / Status LEDs (20)
BUS
Status
U
i
logic voltage
F
S
Error
select
U
O
output voltage
F
N
Error
number
U
S
sensor voltage
23
GB
13
22
14
8
9
21
23
15
16
17
18
54
26
19
24
25
20
8
FE contact
9
FE contact
13 Type plate
14 Label panel BUS IN
15 Connection BUS IN
(M12-a)
16 Label panel
BUS OUT
17 Connection BUS OUT
(M12-a)
18 Rotary encoder switch
(x1)
19 Rotary encoder switch
(x10)
20 Diagnostic / Status LEDs
(see detail drawing)
21 DIN rail mounting
22 Label panel Power
23 Connection Power
24 Label panel RIO
25 Connection RIO (M8)
26 Diagnostic and update
interface
54 Rotary encoder switch
baud rate