General technical data – Burkert Type 0789 User Manual
Page 11

11
Technicaldata/Safeoperation
6.3.5. Type of explosion protection
The composition of the explosion protection code follows the explosion
protection types of the components used in each case:
Solenoid with or without
terminal box
II 2 G Ex d e IIC T4 resp. T5
II 2 D Ex tD A21 IP 65 T135 °C resp.
T100 °C
Solenoid with terminal
box and fuse
II 2 G Ex d e mb IIC T4
II 2 D Ex tD A21 IP65 T135 °C
Solenoid without terminal
box with proximity switch
II 2 G Ex d e ia IIC T4 resp. T5
II 2 D Ex tD A21 IP65 T135 °C resp.
T100 °C
Solenoid with terminal
box, fuse and proximity
switch
II 2 G Ex d e ia mb IIC T4
II 2 D Ex tD A21 IP65 T135 °C
6.4. general Technical data
6.4.1. electrical data
Type
77. - ... - ... - .
78. - ... - ... - .
Temperature class
T4
T5
Type of current
Universal
Universal
rated voltage
24 ... 240 V
24 ... 240 V
Voltage tolerance
+10 % / -10 %
+10 % / -10 %
rated current
0,085 ... 0,014 A
0,085 ... 0,014 A
pick-up current
01,66 ... 0,166 A
01,66 ... 0,166 A
pick-up power
40 W
40 W
power consumption for
holding in equilibrium
3 W
3W
max. number of
switching actuations ca
20 / min
10 / min
6.4.2. electrical connection
Version
code
execution
internal
code
PD30*
* Permanently installed rubber sheathed
cable of Type H05 RN-F3G0.75
****JWxx
english
PTB 03 ATEX 1030 X