2 technical characteristics, Roe-ii – DE DIETRICH ROE-II _ ROE-H User Manual
Page 6
6
ROE-II / ROE-H
13/01/2011 - 300019360-001-I
3.2 Technical characteristics
ROE-II
Conditions of use:
Limit operating temperatures in Hot mode:
- Water: +25 °C / +54 °C
- Outside air: -15 °C / +30 °C
Limit operating temperatures in Cooling mode:
- Water: +18 °C / +22 °C
- Outside air: +18 °C / +42 °C
Maximum operating pressure: 3 bar
(1)
Hot mode : Outside air temperature: +7 °C,
Water temperature at the outlet: +35 °C
Cooling mode : Outside air temperature: +35 °C,
Water temperature at the outlet: +18 °C
(2)
Optional package EH87 to limit start-up intensity
(3)
5 m from the appliance, 1.5 m from the ground, free field, direction
factor 2.
(4)
except QUADROPAC / OECOSUN-R 500
ROE-II
6 MR
8 MR
10 MR
13 MR
10 TR
13 TR
17 TR
(4)
package
EH 70
EH 71
EH 72
EH 69
EH 73
EH 74
EH 75
Output
Calorific output
(1)
kW
6.22
8.11
10.39
10.21
13.17
13.79
17.22
COP hot
(1)
3.47
3.6
3.45
3.75
4.11
3.95
4.01
Absorbed electrical power
kWe
1.79
2.25
3.01
2.72
3.2
3.5
4.29
Cooling output
(1)
kW
6.07
8.14
9.61
15.37
9.6
14.5
17.76
COP cooling
(1)
2.73
2.94
2.58
3.57
2.77
3.01
3.43
Absorbed electrical power
kWe
2.22
2.77
3.72
4.30
3.47
4.82
5.18
Nominal water flow
m
3
/h
1.5
1.43
1.76
2.33
1.75
2.38
2.97
Water resistance
(Nominal water flow)
mbar
126
185
132
175
132
184
215
Air flow rate
m
3
/h
2540
2970
2970
4560
2970
5080
5940
Electrical connection
Power supply voltage
V
230 V ~
230 V ~
230 V ~
230 V ~
400 V 3~
400 V 3~
400 V 3~
Nominal amperage
A
13.4
18.2
22.9
30.7
8.3
11.2
12.7
Start-up amperage
A
22
29
39
43
(2)
48
(2)
64
(2)
74
(2)
Miscellaneous
Sound output
dBA
66
69
73
73
73
73
75
Sound pressure level at 5 m
(3)
dBA
44
47
51
51
51
51
53
R 410 A refrigerant
kg
1.37
1.6
1.62
3.2
1.62
2.67
3.2
Weight (empty) - outside unit
kg
76
82
85
139
85
125
140
Weight (empty) - Indoor module
kg
72
72
72
72
72
72
72