4.6 Electrical connection

Connections must be made by a qualified technician.

The installation must be fitted with a main switch.

Earth the appliance before making any electrical
connections.

Make the electrical connections of the appliance according to:
- the instructions of the prevailing standards,
- the instructions on the circuit diagrams provided with the

appliance,

- the recommendations in the instructions.

Earthing shall comply with standard NFC 15100 (France) or RGBT
(Belgium).
Power the appliance via a circuit which includes a remote omnipolar
switch with a gap of more than 3 mm.
- Single phase models: 230 V (+6% / -10%) 50 Hz
- Three phase models: 400 V (+6% / -10%) 50 Hz

Three phase models must always be fitted with neutral.

4.6.1

Recommended cable cross section

The electrical characteristics of the mains power supply available
must correspond to the values given on the rating plate.

The cable will be carefully chosen according to the following
information:
- Maximum amperage on the thermodynamic unit. See table below.
- Distance of the appliance from the original power supply.
- Upstream protection.
- Neutral operating conditions.

S-C: Cable cross section
DJ: Circuit breaker
Motor : Curve D - Differential protection

Appliance

Absorbed

electrical

power

Nominal

amperage

Start-up

amperage

Type

PAC power supply

Electricity supply Diematic

Communication BUS

kW

A

A

S-C:

Curve D

DJ:

S-C:

Curve C

DJ:

S-C:

ROE-II 6 MR

1,66

13,4

22

Single phase

3x4

16A

3x1.5

10A

2x0.75

8 MR

2,16

18,2

29

Single phase

3x4

20A

3x1.5

10A

2x0.75

10 MR

2,82

22,9

39

Single phase

3x6

25A

3x1.5

10A

2x0.75

10 TR

2,63

8,3

48

Three-phase

5x4

16A

3x1.5

10A

2x0.75

13 MR

3,44

30,7

43

Single phase

3x10

32A

3x1.5

10A

2x0.75

13 TR

3,45

11,2

64

Three-phase

5x4

16A

3x1.5

10A

2x0.75

17 TR

4,19

12,7

74

Three-phase

5x4

16A

3x1.5

10A

2x0.75

ROE-H 13 MH

3,75

33,2

45

Single phase

3x10

40A

3x1.5

10A

2x0.75

13 TH

3,30

14,22

64

Three-phase

5x6

16A

3x1.5

10A

2x0.75

17 TH

4,85

16,8

70

Three-phase

5x10

20A

3x1.5

10A

2x0.75

Electrical back-up

S-C:

DJ:

Three-phase 2 x 6 kW - 400 V AC

5x2.5 mm²

C20

Single phase 1 x 3 kW - 230 V AC

3x6 mm²

C32

Single phase 2 x 3 kW - 230 V AC

3x6 mm²

C32