Operating limits

„

Heating mode ROE-II

Minimum water return temperature for start-up : +5 °C
Minimum water return temperature when operating :
- Water/glycol (antifreeze): +5 °C
- Pure water: +20 °C

Maximum water inlet temperature : 70 °C

„

Heating mode ROE-H

Minimum water return temperature for start-up : +5 °C
Minimum water return temperature when operating :
- Water/glycol (antifreeze): +5 °C
- Pure water: +20 °C (Underfloor heating), +25 °C (Radiator)

Maximum water inlet temperature : 60 °C

„

ROE-II: Cooling mode (except QUADROPAC /
OECOSUN-R 500)

Maximum water return temperature for start-up: 30 °C

Water outlet temperature (°C)

Outside temperature (°C)

30 % glycol mix

Pure water

Water outlet temperature (°C)

Outside temperature (°C)

30 % glycol mix

Pure water

0

20

-15

20

20

54

43

M001663-B

25

48

60

65

-20 -15-12

25

45

2

1

4

3

Water outlet temperature (°C)

Outside temperature (°C)

30 % glycol mix

Pure water