Control system sequence, Return to the factory settings – DE DIETRICH KALIKO TWH 200E - TWH 300E - TWH 300EH User Manual
Page 53
Parameters Description
Adjustment range Factory
setting
P 26
Antilegionella function. The tank is overheated every Saturday from 1 o’clock to
6 o’clock (65 °C).
4
0 = Off
4
1 = Activated outside holiday periods
4
2 = Always activated
0 - 1
0
P 27
Compressor cut-off hysteresis in relation to the set point for the bottom domestic
hot water temperature sensor (only in Auto or Boost mode)
5 - 15
10
P 28
Maximum DHW temperature (bottom sensor) for compressor cut-off (°C) (only
in Auto or Boost mode)
35 - 50
45
P 29
Minimum duration of compressor operation (minutes)
3 - 10
3
P 30
Anti-short-cycle period between 2 compressor start-ups (minutes)
5 - 10
5
P 31
Hydraulic additional heating
4
0 = contact R6 closed if there is an additional hydraulic heating request
4
1 = contact R6 opened if there is an additional hydraulic heating request
0 - 1
0
P 32
DHW setpoint used for the antilegionella function
55 to 70 °C
65 °C
5.7.3.
Control system sequence
Control system sequence
Status Sub-status Operation
0
0
Appliance off
7
Compressor post-operation
1
1
Anti-short cycle activated
2
Wait for the start-up condition for domestic hot water production
3
Start-up of the fan and the defrosting valve
2
5
Compressor starts
6
Defrosting
3
1
Anti-short cycle activated
4
Additional heating starts
7
Compressor post-operation
4
5
Compressor starts
6
Defrosting
9
--
Blockage state
5.7.4.
Return to the factory settings
1. Press the ( and ) keys simultaneously for 5 seconds. The
rSt
menu is displayed.
C003495-B
3
1
4
3
4
1
2
MENU
MODE
TWH 200E TWH 300E TWH 300EH
5. Commissioning
03/02/2014 - 300026515-001-03
51