TRANSDUCERS

Type

Compression mode Ultrasonic; 625 kHz.

Housing Materials

Standard Clamp-on

NEMA 6* (IP 67)

-40 °F to +250 °F (-40 °C to +121 °C)

CPVC, Ultem®, Nylon, PVC (Cable Jacket), Aluminum (small pipe)

High Temperature Clamp-on

NEMA 4 (IP 65)

-40 °F to +400 °F (-40 °C to +204 °C)

Vespel®, Anodized Aluminum, Nickel-plated Brass, Teflon®, (Cable Jacket), Aluminum (small pipe)

Doppler Probe

NEMA 6* (IP 67)

700 PSI (48 Bar) maximum

-40 °F to +210 °F (-40 °C to +99 °C)

316 Stainless Steel, Ultem®, Viton®, Nylon, PVC (Cable Jacket),

Optional Flexible Armored Conduit

Zinc-plated steel, PVC

* Tested to a depth of 1 meter for 30 minutes.

Pipe Sizes

Standard Clamp-on: 1 inch (25 mm) and larger.
Small Pipe Clamp-on: ¼ inch to 1 inch (6 mm to 25 mm).
Insertion Probe: 4 inches to 120 inches (101 mm to 3050 mm).

Cable Length

Up to 990 ft (300 meters) Standard lengths 20, 50, 100 ft (6, 15, 30 meters), 78 ohm Twinax cable.
Optional lengths: to 990 feet (297 meters), 75 ohm RG59 cable.

TABLE A 1.1 - SPECIFICATIONS