Iso -mod, Iso-mod, Control relay output module – Dynasonics DDFXD Doppler Ultrasonic Flow Meter User Manual

Page 34: Rtu/plc monitor remove jumpers

background image

34

06-DPP-UM-00147 02/12

OUT (-)

IN (+)

I/O: 4-20 mA

P.N. D020-1045-100

ISO-MOD

JP2

JP1

INT PWR

EXT PWR

RTU/PLC

MONITOR

Remove

Jumpers

4-20 mA IN (+)

4-20 mA OUT (-)

FIGURE 3.10C - EXTERNALLY POWERED 4-20 mA

CONTROL RELAY OUTPUT MODULE

Two independent SPDT (single-pole, double-throw, Form C) relays are contained in this module. The
relay operations are user configured via the front panel to act in either a flow rate alarm, error alarm or
totalizing pulse. The relays are rated for 200 VAC maximum and have a current rating of 0.5 A resistive
load (175 VDC @ 0.25 A resistive). It is highly recommended that a secondary relay be utilized whenever
the Control Relay ISO-MOD is used to control inductive loads such as solenoids and motors.

Typical relay connections are illustrated in Figure 3.11A. The reed relays located within the relay module
can interface directly with small pilot lights, PLCs, electronic counters and SCADA systems.

Figure 3.11B describes the connection of an external power relay to the Relay ISO-MOD. It is recom-
mended that external power relays are utilized whenever the load to be switched exceeds the switch
rating of the reed relays, or if the load is inductive in nature.

b NO

b CM

b NC

a NO

a CM

a NC

I/O: RE L AY

P.N. D020-1045-102

ISO

-MOD

INTERNAL

CURCUIT

FLOW OK

LOW FLOW

EXTERNAL

TOTALIZER/SAMPLER

P

FIGURE 3.11A - TYPICAL RELAY CONNECTIONS