EXTERNAL LOAD CALCULATIONS FOR DIRECT BURIED CONDUIT

25701 Science Park Drive

Cleveland, Ohio 44122

216-464-3400

1-800-3CARLON (322-7566)

www.carlon.com

THE MOMENT OF INERTIA (I) EQUALS THE WALL THICKNESS (t) CUBED,

DIVIDED BY TWELVE (12). I = t

3

/12.

THE MEAN RADIUS (r) EQUALS THE OUTSIDE DIAMETER (O.D.) MINUS

THE WALL THICKNESS (t) DIVIDED BY TWO (2). r = (O.D. - t)/2

PIPE STIFFNESS FOR DB60 IS EQUAL TO 60 lb/in

2

AND FOR DB120 IS

EQUAL TO 120 lb/in

2

. 4” SCHEDULE 40 CONDUIT WILL HAVE A PIPE

STIFFNESS OF 346 lb/in

2

(MINIMUM WALL THICKNESS).

MATERIALS SUITABLE FOR FOUNDATION AND EMBEDMENT ARE

DEFINED ACCORDING TO THE UNIFIED SOIL CLASSIFICATION SYSTEMS

(USCS) IN ASTM D2487, “STANDARD METHOD FOR CLASSIFICATION OF

SOILS FOR ENGINEERING PURPOSES”. BEDDING SOIL MODULUS (E

1

)

SHALL BE 2000 LB/IN

2

FOR CLASS IA AND IB SOILS AND 1000 LB/IN

2

FOR

CLASS III SOIL. CLASS IA MATERIALS PROVIDE MAXIMUM STABILITY AND

PIPE SUPPORT FOR A GIVEN DENSITY DUE TO ANGULAR INTERLOCK OF

PARTICLES. CLASS III MATERIALS PROVIDE LESS SUPPORT FOR A

GIVEN DENSITY THAN CLASS I MATERIALS. HIGH LEVELS OF

COMPACTIVE EFFORT MAY BE REQUIRED UNLESS MOISTURE CONTENT

IS CONTROLLED.

DEAD LOAD (DL) IS EQUAL TO THE UNIT WEIGHT OF THE BACKFILL ( γ)

TIMES THE HEIGHT OF COVER (H) DIVIDED BY 144.

DL = γγγγ * H/144