Ordering information

Fluke-434-II

Three-Phase Energy Analyzer

Fluke-435-II

Three-Phase Power Quality and Energy Analyzer

Fluke-437-II

400 Hz Three-Phase Power Quality and Energy Analyzer

Optional/replacement accessories

I430-FLEXI-TF-4PK 6000 A Fluke 430 Thin Flexi 61 cm (24 in) 4 pack

C437-II

Hard Case 430 Series II with roller

C1740

Softcase for 174X and 43X-II PQ Analyzer

i5sPQ3

i5sPQ3, 5 A ac Current Clamps, 3-pack

i400s

i400s AC Current Clamp

WC100

WC100 Color Localization Set

GPS430-II

GPS430 Time Synchronization Module

BP291

Double capacity Li-ion battery (up to 16 hr)

HH290

Hanging hook for use on cabinet doors

Fluke Corporation

PO Box 9090, Everett, WA 98206 U.S.A.
Fluke Europe B.V.

PO Box 1186, 5602 BD

Eindhoven, The Netherlands

Fluke.

Keeping your world up and running.

®

For more information call:

In the U.S.A. (800) 443-5853 or

Fax (425) 446-5116

In Europe/M-East/Africa +31 (0) 40 2675 200 or

Fax +31 (0) 40 2675 222

In Canada (800)-36-FLUKE or

Fax (905) 890-6866

From other countries +1 (425) 446-5500 or

Fax +1 (425) 446-5116

Web access: http://www.fluke.com

©2006, 2011 Fluke Corporation.

Specifications subject to change without notice.

Printed in U.S.A. 8/2011 2643006D D-EN

Pub ID 11858-eng

Modification of this document is not

permitted without written permission

from Fluke Corporation.

Flexible Current Probe i430 Flexi-TF specification

General specifications
Probe and cable material

Alcryn 2070NC, reinforced insulation, UL94 V0, Color: RED

Couplings material

Lati Latamid 6H-V0 Nylon

Probe cable length

610 mm (24 in)

Probe cable diameter

12.4 mm (0.49 in)

Probe cable bend radius

38.1 mm (1.5 in)

Output cable length

2.5 meters RG58

Output connector

Safety BNC connector

Operating range

-20 °C to +90 °C

Storage temperature

-40 °C to +105°C

Operating humidity

15 % to 85 % (non condensing)

Degree of protection (Probe)

IP41

Specifications
Current range

6000 A AC RMS

Voltage output (@1000 ARMS, 50 Hz)

86.6 mV

Accuracy

± 1 % of reading (@ 25 °C, 50 Hz)

Linearity (10 % to 100 % of range)

± 0.2 % of reading

Noise (10 Hz – 7 kHz)

1.0 mV ACRMS

Output impedance

82 Ω min

Load impedance

50 MΩ

Internal Resistance per 100 mm probe

length

10.5Ω ± 5 %

Bandwidth (-3dB)

10 Hz to 7 kHz

Phase error (45 Hz – 65 Hz)

± 1°

Position sensitivity

± 2 % of reading max.

Temperature coefficient

± 0.08 % max of reading per °C

Working voltage

(see safety standards section)

1000 V AC RMS or DC (head)

30 V max. (output)