Measurement modes, Display modes, Input characteristics – Atec Fluke-430 Series User Manual
Page 4
4 Fluke Corporation Fluke 430 Series II Three-Phase Energy and Power Quality Analyzers
Measurement modes
Scope
4 voltage waveforms, 4 current waveforms, Vrms, Vfund. Arms, A fund, V @ cursor, A @ cursor, phase angles
Volts/amps/hertz
Vrms phase to phase, Vrms phase to neutral, Vpeak, V Crest Factor, Arms Apeak, A Crest Factor, Hz
Dips and swells
Vrms½, Arms½, Pinst with programmable threshold levels for event detection
Harmonics dc, 1 to 50, up to 9th harmonic
for 400 Hz
Harmonics Volts, THD, Harmonic Amps, K factor Amps, Harmonic Watts, THd Watts, K factor Watts, Interharmonic
Volts, Interharmonic Amps, Vrms, Arms (relative to fundamental or to total rms)
Power and energy
Vrms, Arms, Wfull, Wfund., VAfull, VAfund., VAharmonics, VAunbalance, var, PF, DPF, CosQ, Efficiency factor,
Wforward, Wreverse
Energy loss calculator
Wfund, VAharmonics, VAunbalance, var, A, Loss Active, Loss Reactive, Loss Harmonics, Loss Unbalance, Loss
Neutral, Loss Cost (based upon user defined cost / kWh)
Inverter efficiency
(requires optional dc current clamp)
Wfull, Wfund, Wdc, Efficiency, Vdc, Adc, Vrms, Arms, Hz
Unbalance
Vneg%, Vzero%, Aneg%, Azero%, Vfund, Afund, V phase angles, A phase angles
Inrush
Inrush current, Inrush duration, Arms½, Vrms½
Monitor
Vrms, Arms, harmonic Volts, THD Volts, PLT, Vrms½, Arms½, Hz, dips, swells, interruptions, rapid voltage changes,
unbalance and mains signalling.
All parameters are measured simultaneously in accordance with EN50160
Flagging is applied according to IEC61000-4-30 to indicate unreliable readings due to dips or swells
Flicker (435-II and 437-II only)
Pst(1min), Pst, Plt, Pinst, Vrms ½, Arms ½, Hz
Transients (435-II and 437-II only)
Transient waveforms 4x Voltage 4x Amps, triggers: Vrms ½, Arms ½, Pinst
Mains Signaling (435-II and 437-II only)
Relative signaling voltage and absolute signaling voltage averaged over three seconds for up to two selectable
signaling frequencies
Power Wave (435-II and 437-II only)
Vrms½, Arms½ W, Hz and scope waveforms for voltage amps and watts
Logger
Custom selection of up to 150 PQ parameters measured simultaneously on 4 phases
Sampling system
Resolution
16 bit analog to digital converter on 8 channels
Maximum sampling speed
200 kS/s on each channel simultaneously
RMS sampling
5000 samples on 10/12 cycles according to IEC61000-4-30
PLL synchronization
4096 samples on 10/12 cycles according to IEC61000-4-7
Nominal frequency
434-II and 435-II: 50 Hz and 60 Hz
437-II: 50 Hz, 60 Hz and 400 Hz
Display modes
Waveform display
Available in all modes via SCOPE key
435-II and 437-II: Default display mode for Transients function
Update rate 5x per second
Displays 4 cycles of waveform data on screen, up to 4 waveforms simultaneously
Phasor diagram
Available in all modes via Scope waveform display
Default view for Unbalance mode
Meter readings
Available in all modes except Monitor and Transients, provides tabulated view of all available readings
Fully customizable up to 150 readings for Logger mode
Trend graph
Available in all modes except Transients
Single vertical cursor with min max and avg reading at cursor position
Bar graph
Available in Monitor and Harmonics mode
Event list
Available in all modes
Provides 50/60** cycles of waveform information and associated 1/2 cycle rms values for Volts and Amps
Input characteristics
cont.