3 Fluke Corporation Fluke 430 Series II Three-Phase Energy and Power Quality Analyzers

Technical specifications

Specifications are valid for models Fluke 434-II, Fluke 435-II, Fluke 437-II unless otherwise specified.

Specificatons for Amp and Watt readings are based upon i430-Flexi-TF unless otherwise specified.

Input characteristics

Voltage inputs
Number of inputs

4 (3 phase + neutral) dc-coupled

Maximum input voltage

1000 Vrms

Nominal voltage range

Selectable 1 V to 1000 V

Max. peak measurement voltage

6 kV (transient mode only)

Input impedance

4 MΩ//5 pF

Bandwidth

> 10 kHz, up to 100 kHz for transient mode

Scaling

1:1, 10:1, 100:1, 1,000:1 10,000:1 and variable

Current inputs
Number of inputs

4 (3 phase + neutral) dc- or ac-coupled

Type

Clamp or current transformer with mV output or i430flex-TF

Range

0.5 Arms to 600 Arms with included i430flex-TF (with sensitivity 10x)

5 Arms to 6000 Arms with included i430flex-TF (with sensitivity 1x)

0.1 mV/A to 1 V/A and custom for use with optional ac or dc clamps

Input impedance

1 MΩ

Bandwidth

> 10 kHz

Scaling

1:1, 10:1, 100:1, 1,000:1 10,000:1 and variable

430 Series II Power Quality and Energy Analyzer selection table

Model

Fluke 434-II

Fluke 435-II

Fluke 437-II

Standard compliance

IEC 61000-4-30 Class S IEC 61000-4-30 Class A IEC 61000-4-30 Class A

Volt Amp Hz

Dips and swells

Harmonics

Power and energy

Energy loss calculator

Unbalance

Monitor

Inrush

Event waveform capture

Flicker

Transients

Mains signaling

Power wave

Power inverter efficiency

400Hz

C1740 Soft Case

C437-II Hard Case with rollers

SD card (Max 32 GB)

8 GB

8 GB

8 GB

All models include the following accessories TL430 test lead set, 4 x i430 thin flexi current probes, BP290 battery, BC430 power adapter with international power adapter set, USB cable

A-B mini and PowerLog CD.