The Raptor System: Features

MASTER UNIT’S FEATURES

The Raptor MS is the master unit of any Raptor configuration. It provides the connection for the touch screen console and can be used as stand-alone for
primary test applications that do not require extremely high current/power. When slave units are added, the MS will detect them automatically over the infrared
link and will accommodate the system’s parameters with no intervention from the user:
Regulated high AC current output. Able to inject up to 3.8kA (with 3kVA) indefinitely or 9.5kA (with 2kVA) during 3s. Up to 15kA when combined with one or

more slave units.

Regulated AC auxilliary output. Working in current mode is capable of injecting up to 9 A indefinitely or 35A for 3s. Working in Voltage mode is capable of

generating voltage up to 200V AC.

Voltmeter Input. Ranges: 0.2, 2, 20 or 300Vac/dc (auto or manual). Built-in phase angle meter.

Ammeter input. Ranges: 0.2, 2 or 20Aac/dc (auto or manual). Built-in phase angle meter.

Low signal Voltmeter. Ranges: 30, 300 or 3000 mVac/dc (auto or manual). Built-in phase angle meter.

Binary input: Voltage or dry contact with reversible logic (NO, NC) and auto-detection.

LEDs: Monitor overload, temperature, status of communications, standby, digital input, power output and power supply.

IRDA interface: Interconnects Slave units to the Master wirelessly.

SLAVE UNIT’S FEATURES

The Raptor SL features toroidal windings that are activated individually by the master unit as the power demand grows, through a sophisticated injection control
that ensures seamless current flow and optimal workload distribution.
The slave Raptor is visually identical to the master unit but lacks the measurement section, the handheld controller and the auxiliary input/output panels. Its
mission is to push an additional 5 kVA power to the high current pass-through secondary. Up to three slaves can be added for up to 15,000 A with a 18-kVA
total injection power. The master unit detects the presence of slaves using infrared communications, so no additional control or power interconnections are
required. The user only needs to pass the current cables across the entire assembly and use it as if it was a single device, in a fully transparent way to the
user. As an added benefit of the pass-through secondary technique, the user can easily multiply the compliance voltage by making more than one turn with the
current conductor around the entire system.