ODEN AT

Primary Current Injection Test System

S or X units
H units

p = units in parallel, s = units in series
*) Voltage between output terminals

Output voltage* (V)

High current output - ODEN AT systems for 240 V, 50 Hz

Current (kA)

High current output - ODEN AT systems for 400 V, 50 Hz

Output voltage* (V)

Current (kA)

High current output - ODEN AT systems for 480 V, 60 Hz

Output voltage* (V)

Current (kA)

ODEN AT, 480 V mains voltage, 60 Hz

Open
circuit
voltage

Max.
continuous
current 3)

Max. cur-
rent, 3 mi-
nutes 3)

Max.
current,
1 sec 3)

ODEN AT/1S

7.2 V

1000 A

2000 A

7000 A

ODEN AT/2S

1)

7.2 V

1900 A

4000 A

13 kA

2)

14.4 V

900 A

2000 A

6000 A

ODEN AT/3S

1)

7.2 V

1900 A

4000 A

13 kA

2)

21.6 V

600 A

1400 A

4400 A

ODEN AT/1X

High cur-
rent output

7.2 V

1000 A

2000 A

7000 A

Output 0 – 30/60 V

30 V range

36 V

160 A

300 A

1200 A

60 V range

72 V

80 A

150 A

600 A

ODEN AT/2X

High cur-
rent output

1)

7.2 V

1900 A

4000 A

13 kA

2)

14.4 V

900 A

2000 A

6000 A

Output 0 – 30/60 V

30 V range

1)

36 V

320 A

600 A

2500 A

60 V range

1)

272 V

160 A

300 A

1200 A

60 V range

2)

144 V

80 A

150 A

600 A

ODEN AT/3X

High cur-
rent output

1)

7.2 V

1900 A

4000 A

13 kA

2)

21.6 V

600 A

1400 A

4400 A

Output 0 – 30/60 V

30 V range

1)

36 V

380 A

850 A

2600 A

30 V range

2)

108 V

120 A

290 A

880 A

60 V range

2)

216 V

60 A

145 A

440 A

ODEN AT/1H

4.3 V

1250 A

2600 A

11 kA

ODEN AT/2H

1)

4.3 V

2500 A

5300 A

21 kA

2)

8.7 V

1250 A

2500 A

10.9 kA

ODEN AT/3H

1)

4.3 V

3800 A

7700 A

21.9 kA

2)

13.0 V

1250 A

2600 A

7200 A

1) Current units connected in parallel
2) Current units connected in series
3) Maximum possible current is also limited by the impedance in the test circuit. The

current value can not exceed output voltage / impedance value.