Oden at primary current injection test system – Atec Megger-ODEN-AT User Manual
Page 5
![background image](/manuals/318972/5/background.png)
ODEN AT
Primary Current Injection Test System
S or X units
H units
p = units in parallel, s = units in series
*) Voltage between output terminals
Output voltage* (V)
High current output - ODEN AT systems for 240 V, 50 Hz
Current (kA)
High current output - ODEN AT systems for 400 V, 50 Hz
Output voltage* (V)
Current (kA)
High current output - ODEN AT systems for 480 V, 60 Hz
Output voltage* (V)
Current (kA)
ODEN AT, 480 V mains voltage, 60 Hz
Open
circuit
voltage
Max.
continuous
current 3)
Max. cur-
rent, 3 mi-
nutes 3)
Max.
current,
1 sec 3)
ODEN AT/1S
7.2 V
1000 A
2000 A
7000 A
ODEN AT/2S
1)
7.2 V
1900 A
4000 A
13 kA
2)
14.4 V
900 A
2000 A
6000 A
ODEN AT/3S
1)
7.2 V
1900 A
4000 A
13 kA
2)
21.6 V
600 A
1400 A
4400 A
ODEN AT/1X
High cur-
rent output
7.2 V
1000 A
2000 A
7000 A
Output 0 – 30/60 V
30 V range
36 V
160 A
300 A
1200 A
60 V range
72 V
80 A
150 A
600 A
ODEN AT/2X
High cur-
rent output
1)
7.2 V
1900 A
4000 A
13 kA
2)
14.4 V
900 A
2000 A
6000 A
Output 0 – 30/60 V
30 V range
1)
36 V
320 A
600 A
2500 A
60 V range
1)
272 V
160 A
300 A
1200 A
60 V range
2)
144 V
80 A
150 A
600 A
ODEN AT/3X
High cur-
rent output
1)
7.2 V
1900 A
4000 A
13 kA
2)
21.6 V
600 A
1400 A
4400 A
Output 0 – 30/60 V
30 V range
1)
36 V
380 A
850 A
2600 A
30 V range
2)
108 V
120 A
290 A
880 A
60 V range
2)
216 V
60 A
145 A
440 A
ODEN AT/1H
4.3 V
1250 A
2600 A
11 kA
ODEN AT/2H
1)
4.3 V
2500 A
5300 A
21 kA
2)
8.7 V
1250 A
2500 A
10.9 kA
ODEN AT/3H
1)
4.3 V
3800 A
7700 A
21.9 kA
2)
13.0 V
1250 A
2600 A
7200 A
1) Current units connected in parallel
2) Current units connected in series
3) Maximum possible current is also limited by the impedance in the test circuit. The
current value can not exceed output voltage / impedance value.