ODEN AT

Primary Current Injection Test System

Specifications ODEN AT

Specifications are valid at nominal input voltage and an ambient
temperature of +25°C, (77°F). Specifications are subject to change
without notice.

System designation

An ODEN AT-system consists of a control unit and one, two or
three current units. There are three different versions of the current
units: S-unit (standard), X-unit (extra 30/60 V outlet) and H-unit
(high current). The system designation indicates the number and
version of current units included.
Example: ODEN AT/2X

2 = Number of current units

X = Version of current unit (S, X or H)

Environment

Application field

The instrument is intended for use
in high-voltage substations and
industrial environments.

Temperature

Operating

0°C to +50°C (+32°F to +122°F)

Storage & transport

-25°C to +55°C (-13°F to +127°F)

Humidity

5% – 95% RH, non-condensing

CE-marking

LVD

2006/95/EC

EMC

2004/108/EC

General

Mains voltage

240 / 400 V AC, 50 / 60 Hz
480 V AC / 60 Hz

Mains inlet

IEC 60309-2, 63 A

Input current

Output current x open circuit voltage
/ input voltage

Protection

The output transformer has a built-in
thermal cut-out, and the primary
side is protected by a miniature
circuit breaker.

Dimensions

Control unit AT

570 x 310 x 230 mm
(22.4” x 12.2” x 9”)

Current unit S, X H

570 x 310 x 155 mm
(22.4” x 12.2” x 6”)

Complete with cart

690 x 350 x 860 mm
(27.2” x 13.8” x 33.9”)

Weight

Control unit AT

25 kg (55 lbs)

Current unit S

42 kg (92.6 lbs)

Current unit X

45 kg (99.3 lbs)

Current unit H

49 kg (108 lbs)

Cart

11 kg (24.3 lbs)

Display

LCD

Available languages

English, German, French, Spanish,
Swedish.

Measurement section

Ammeters

Measurement method

AC, true RMS

Inaccuracy

1% of range ±1 digit

Ammeter 1
Ranges

0 – 4800 A / 0 –15 kA
0 – 9600 A / 0 – 30 kA
0 – 960 A / 0 – 3 kA

Ammeter 2
Ranges

0 – 2.000 A / 0 – 20.00 A

Maximum current

20 A (The input is not protected by
a fuse)

Voltmeter

Measurement method

AC, true RMS

Ranges

0 – 0.2 V, 0 – 2 V, 0 – 20 V,
0 – 200 V, AUTO

Inaccuracy

1% of range ±1 digit

Input resistance (Rin)

240 kΩ (range 0 – 200 V)
24 kΩ (other ranges)

Dielectric withstand

2.5 kV

Timer

Presentation

In seconds, mains frequency cycles
or hours and minutes

Ranges

0.000 – 999.9 s
0 – 9999 cycles
0.001 s – 99 h 59 min

Inaccuracy

±(1 digit + 0.01% of value)
For the stop condition in INT-mode
1 ms shall be added to the specified
measurement error.

Stop input

Max. input voltage

250 V AC / 275 V DC

Phase angle

Range

0 – 359º

Resolution

Inaccuracy

±2º (for voltage and current readings
that are higher than 10% of the
selected range)

Z, P, R, X, S, Q and power factor (cos

φ)

For these measurements the result is calculated using U, I and
sometimes

φ.

Imax

Stores highest current value that exists ≥100 ms

INT-level

Threshold indicating that current is interrupted. Can be set to
0.7% or 2.1% of Ammeter 1 range.