Tech menus – Alpha Technologies Spectra Series User Manual
Page 38

Preliminary Operating Instructions 38 of 62 AIP SERVICE NUMBER 1-800-863-3364
AC Low Armed or Disarmed ---------------------------------------“AC Lo Armed
→”
---------------------------------------------------------------------------“AC
Lo
Disarmed
→”
DC High Armed or Disarmed --------------------------------------“DC Hi Armed
→”
---------------------------------------------------------------------------“DC
Hi
Disarmed
→”
DC Low Armed or Disarmed ---------------------------------------“DC Lo Armed
→”
---------------------------------------------------------------------------“DC
Lo
Disarmed
→”
DC Failure Armed or Disarmed------------------------------------“DCFail Armed
→”
---------------------------------------------------------------------------“DCFail
Disarmed
→”
Ground Fault Indicator------------------------------------------------“GFI Armed
→”
Armed or Disarmed ------------------------------------------------“GFI Disarmed
→”
End of Discharge ------------------------------------------------------“EOD Armed
→”
Armed or Disarmed ------------------------------------------------“EOD Disarmed
→”
DC High Volts per Cell Set point -----------------------------------“DC Hi 2.50V/C
→”
DC
High
Set
point
Tenths ----------------------------------------“DC Hi 2.50V/C ”
DC High Set point Hundredths ----------------------------------“DC Hi 2.50V/C ”
High DC Lockout Volts per Cell Set point -----------------------“HiLoc 2.50V/C
→”
High DC Lockout Volts Set point Tenths----------------------“HiLoc 2.50V/C ”
High DC Lockout Volts Set point Hundredths ---------------“HiLoc 2.50V/C “
DC Low Volts per Cell Set point------------------------------------“DC Lo 2.10V/C
→”
DC Low Volts Set point Tenths----------------------------------“DC Lo 2.10V/C ”
DC Low Volts Set point Hundredths ---------------------------“DC Lo 2.10V/C ”
End of Discharge Volts/Cell Set point ----------------------------“EOD 1.70V/C
→”
EOD Volts Set point Tenths --------------------------------------“EOD 1.70V/C ”
EOD Volts Set point Hundredths -------------------------------“EOD 1.70V/C ”
Ground Fault Indicator Set point -----------------------------------“Set GFI Open
→”
GFI Positive Set point ---------------------------------------------“Set GFI Pos
→”
GFI Negative Set point --------------------------------------------“Set GFI Neg
→”
Equalize Settings-----------------------------------------------------------“Eqlz Settings
→”
Equalize
Time--------------------------------------------------------------“Eqlz
Time 1hr
→”
Equalize Hours of Ones ----------------------------------------------“Eqlz Time 2hr ”
Equalize
Hours
of
Tens ----------------------------------------------“Eqlz Time 10hr ”
Equalize Interval ----------------------------------------------------------“Eqlz Int 1Days
→”
Interval Days of Ones ------------------------------------------------“Eqlz Int 1Days ”
Interval Days of Tens -------------------------------------------------“Eqlz Int 11Days ”
Change Equalize Mode
Manual
Start/Manual Stop Eqlz ---------------------------------“Mode: Man/Man
→”
Manual
Start/Automatic Stop Eqlz---------------------------------“Mode: Man/Auto
→”
Automatic Start/Automatic Stop Eqlz -----------------------------“Mode:Auto/Auto
→”
Select Start in Float or Equalize mode ------------------------------“Start in Float
→”
---------------------------------------------------------------------------“Start in Eqlz
→”
Hours Run --------------------------------------------------------------------“Hrs Run 12:34”
Internal Charger Temperature in ºC or °F --------------------------“InTemp 29.00ºC
→”
---------------------------------------------------------------------------“InTemp 84.20°F
→”
Optional External Temperature in ºC or °F ------------------------“ExTemp 29.00ºC
→”
---------------------------------------------------------------------------“ExTemp
84.20°F
→”
Time ---------------------------------------------------------------------------“Mon 06:00:00 AM ”
Set
Time---------------------------------------------------------------------“Time Mon 06:00A
→”
Change
Weekday------------------------------------------------------“TIME:
Mon 06:00A”
Change
Hours ----------------------------------------------------------“TIME: Mon 06:00A”
Change
Mins ------------------------------------------------------------“TIME: Mon 06:00A”
Change
AM/PM --------------------------------------------------------“TIME: Mon 06:00A”
Charger Pause --------------------------------------------------------------“Pause 00 mins
→”
Charger Pause in minutes of Tens --------------------------------“Pause 10 mins “
Charger Pause in minutes of Ones -------------------------------“Pause 10 mins “
Days Till Next Eqlz ---------------------------------------------------------“Next Eqlz 0.00”
TECH MENUS:
Control Board Version----------------------------------------------------“Prod ?? MM/DD/YY”
Optional ALARM I/O Relay Test Start -------------------------------“Relay Start
→”
Optional ALARM I/O Relay Test Stop--------------------------------“Relay Stop
→”