2.5 Connecting the External Alarm Port

An external alarm panel can be connected to the external alarm port (Figure 2.7). The port’s
contacts are rated at 30 VDC at 1 Amp.

An Emergency Power Off (EPO) switch is created by wiring a switch to Pins 7 and 8.

• The switch must be a SPST, N.O. type and be electrically isolated (up to 1500 VAC

isolation is recommended). The connecting cable can be twisted or shielded wire not
more than 100 ft. long.

• The contacts must be shorted for at least 1.5 seconds with unit shutdown about 2 seconds

after the shorting starts.

CAUTION: The EPO switch does not disconnect the utility line. Switch off the circuit
breaker providing line power to the unit.

Figure 2.7

Wiring the External Alarm Port

8

7

6

5

4

3

2

1

EPO

Circuit

Optional
N.O. EPO Switch

N.C. Line

Present

N.C.

Battery OK

N.O. Line

Failure

N.O. Low

Battery Warning

Contact Rating:

30 VDC @ 1 Amp

UPS Internal