Installation
7.2
Electrical connection (motor)
The electrical connection must be carried out
as follows:
according to the applicable national and
local laws and regulations,
according to the applicable system-
dependent prescriptions and requirements,
according to the applicable regulations of
the utility company.
DANGER
Electrical danger!
Malpractice can result in severe
injuries and material damage!
DANGER
Electrical danger!
The electrical connection may be
carried out by trained and
authorized electricians only!
DANGER
Electrical danger!
Before beginning work on the
unit or system, the following
measures must be carried out:
Deenergize.
Secure against being
switched on again.
Determine
whether
deenergized.
Ground and short-circuit.
Cover or block off adjacent
energized parts.
WARNING
Danger due to gauge pressure
and vacuum!
Danger due to escaping fluid!
Before beginning work on the
unit or system:
Interrupt supply of operating
liquid.
Bleed lines and vacuum
pump/compressor
(depressurize).
CAUTION
Incorrect connection of the motor
can lead to serious damage to
the unit!
Observe the motor rating plate.
It is imperative that the operating conditions
correspond to the data given on the rating
plate!
Deviations permissible without reduction in
performance:
±5 % voltage deviation
±2 % frequency deviation
Make the connection in accordance with the
circuit diagram in the terminal box.
Connect the protective conductor.
Use suitable cable lugs when doing so.
The electrical connection must be
permanently safe.
Tightening torques for terminal plate
connections:
Thread
M4 M5
[Nm]
0.8 ... 1.2 1.8 ... 2.5
Tightening
torque
[ft lbs]
0.590 ...
0.885
1.33 ...
1.84
WARNING
Electrical danger!
Clearance between bare live
parts and between bare live parts
and ground:
at least 5.5 mm [0.217"] (at a
nominal voltage of V
n
≤ 690V)
Make sure there are no
protruding pieces of wire!