beautypg.com

Anti-cavitation pressure reducing valve, 01ko, Model – Cla-Val 90-01KO User Manual

Page 5

background image

Anti-Cavitation
Pressure Reducing Valve

High Pressure

Isolation Valve

Gauge

Constant
Downstream
Pressure

CLA-VAL 90-01BYKO

Pressure Reducing Valve

CLA-VAL 90-01ASKO

Pressure Reducing Valve

CLA-VAL Model

90-01KO

Anti-Cavitation Trim

for Excess Pressure Drop

Consult Cavitation Chart

Isolation Valve

Gauge

Constant
Downstream
Pressure

High Pressure

The "D" check feature on a vertically installed 6" and larger valves must be horizontally installed.

Typical Applications

Typical applications include pressure reducing valve station
using Model 90-01BYKO and Model 90-01ASKO in parallel to
handle wide range of flow rates. Larger Model 90-01BYKO valve
meets requirements of peak loads and smaller Model
90-01ASKO handles low flows.

Schematic Diagram

Item Description

1

Hytrol (100-01KO Main Valve)

2

X58 Restriction Fitting

3

CRD Pressure Reducing Control

Optional Features

Item Description

A

X46A Flow Clean Strainer

B

CK2 (Isolation Valve)

C

CV Flow Control (Closing)*

D

Check Valves with Isolation Valve

P

X141 Pressure Gauge

S

CV Speed Control (Opening)

V

X101 Valve Position Indicator

Y

X43 "Y" Strainer

*

The closing speed control (optional) on this valve should

always be open at least three (3) turns off its seat.

Virtually Cavitation Free Operation

Sensitive and Accurate Pressure Control

Easy Adjustment and Maintenance

Tamper Resistant

Optional Check Feature

Fully Supported Frictionless Diaphragm

The Cla-Val Model 90-01KO Anti-Cavitation Hytrol Pressure Reducing
Valve automatically reduces a higher inlet pressure to a steady lower down-
stream pressure, regardless of changing flow rate and/or varying inlet pres-
sure. This valve is an accurate, pilot-operated regulator capable of holding
downstream pressure to a pre-determined limit. When downstream pres-
sure exceeds the pressure setting of the control pilot, the main valve and
pilot valve close drip-tight.

If a check feature is added, and a pressure reversal occurs, the down-
stream pressure is admitted in the main valve cover chamber, closing the
valve to prevent return flow.

Cla-Val Model

90-01KO

Pressure Reducing Valve with Anti-Cavi-

tation Trim provides for optimum downstream pressure control
while reducing noise and eliminating damage associated with cav-
itation.
See Cavitation Guide to determine if the valve is a candidate for
the KO Anti-Cavitation Trim.

90-01KO

MODEL

(Full Internal Port)