Piping, When installing the pump below the tank, When installing the pump above the tank – Pump Solutions Group Neptune Solenoid-driven Diaphragm Metering Pump ARPZ-31_61_12 User Manual

Page 11: Installation

background image

10

Installation

Pump-mounting bolts (2 sets)

Foot valve

Drain cock

Suction-pipe cover

Tank

Relief/air-release hose

Main pipe

Anti-siphon check valve

Injection point

Discharge-
side pipe

Discharge-side joint

Suction-side joint

Suction-side pipe

Relief/air-release port

When a PE or FEP tube is
to be used for the suction
side pipe (FEC/FFC/FTC
only), attach the ceramic
weight (supplied) to
straighten the tube.

3-way valve

PVC

UP

Relief/air-release port

Suction-side joint

3-way valve

Discharge-
side pipe

Discharge-
side joint

Anti-siphon check valve

Relief/air-release hose

Tank

Suction-side pipe

Suction valve

Main pipe

Injection point

Installation is described with an example using PZ-31-VEC and TACMINA tank.
• If the valve has not been opened or clogging by foreign matter has occurred inside the pipe at the discharge side of

the pump, the chemical will gush out from the relief/air-release port. Therefore, always have a relief/air-release hose
installed, and lead its end back into the tank or other container.

• Install a valve for releasing abnormal pressure that has built up inside the discharge-side pipe. The 3-way valve on the

washing water line may be used instead.

Piping

When installing the pump

below the tank

(1) Connect the suction valve of the tank and the suction-

side joint of the pump using the hose/tube.

(2) Connect the discharge-side joint of the pump and

main pipe (injection point) using the tube. When
doing this, attach the anti-siphon check valve at the
injection-point side end of the tube.

(3) Return the end of the relief/air-release hose which

has already been attached to the relief/air-release
port to the tank or other container.

✽ It is also recommended that a valve, meter, etc. be

installed to make it easy to carry out maintenance
and other such jobs.

When installing the pump

above the tank

(1) Using the pump-mounting bolts provided, secure the

pump to the prescribed position on top of the tank.

(2) Pass the suction-side hose/tube with foot valve and

ceramic weight (tube only) attached through the
hole in the suction-pipe cover on top of the tank, and
connect it to the suction-side joint of the pump. At
this time, adjust the length of the hose/tube and cut
it so that the foot valve is 30 mm higher than the bot-
tom of the tank.

(3) Connect the discharge-side joint of the pump and

main pipe (injection point) using the tube. When
doing this, attach the anti-siphon check valve at the
injection-point side end of the tube.

(4) Return the end of the relief/air-release hose which

has already been attached to the relief/air-release
port to the tank or other container.

✽ Installing the pump above the tank is not recommend-

ed for chemicals in which air bubbles tend to form.

✽ This pump’s static suction head is −1.5 m for water.

Its suction capability may decrease when the valve
seats inside the pump head are dry.

✽ Be absolutely sure to connect the foot valve provided

to the end of the suction-side hose/tube to prevent
dirt or foreign matter from entering the pump head
and valve seat area.

✽ It is also recommended that a valve, meter, etc. be

installed to make it easy to carry out maintenance
and other such jobs.

Model for injection of general chemicals: PZ-31/61/12-VEC/VFC/FEC/FFC/FTC