Default
Allowable
Field
Line #
DISPLAY ➀
Value
Range
Value
21
Destaging PSI
Enter pressure to destage in PSI mode after entering system
0
0 -System
pressure span
Span
22
Forced Destg Tmr.
Enter in minutes (0 - 99) value of a timer after which the
pump will be forced to de-stage; ‘0’ disables this function
60
0 - 99
23
GPM Xmiter Span
Enter value equal to GPM transmitter calibration
0
0 - 30,000
24
2nd Stage Proof
2nd pump stage proof time in seconds
2
1 - 999
25
3rd Stage Proof
3rd pump stage proof time in seconds
2
1 - 999
26
Display Watts
Use up/down keys to enter yes or no
Yes
Y/N
27
Three phase Watts
Use up/down keys to enter yes or no,
YES = three phase, NO = single phase
Yes
Y/N
28
Display AMPs
Use up/down keys to enter yes or no
Yes
Y/N
29
Display GPM
Use up/down keys to enter yes or no
No
Y/N
30
1PT Display Variable
Use the up/down keys to select the variable name for
the signal originating from pressure transmitter 1PT:
pressure - 1PT, inlet pressure, return pressure, not used.
Not Used
As Listed
31
1PT Span
Enter value equal to pressure span
100
0 - 999
32
High 1PT Press.
Enter value of the high pressure above which an alarm
will be set
0
0 - 100
33
High 1PT Pr. TMR.
Enter in seconds (0 - 999) value of high pressure proof timer,
‘0’ disables this function
0
0 - 999
34
High 1PT Reset
Enter value of the high reset pressure
0
0 - 100
35
Low 1PT Press.
Enter value of the low pressure below which an alarm will
be set
5
0 - 100
36
Low 1PT Pr. TMR.
Enter in seconds (0 - 999) value of low pressure proof timer;
‘0’ disables this function
20
0 - 999
37
Low 1PT Reset
Enter value of the low reset pressure
10
0 - 100
38
Low 1PT Auto RST
To change the low reset, use UP/DOWN key to enter yes or no
Yes
Y/N
39
2PT Display Variable
Use the up/down keys to select the variable name for the
signal originating from pressure transmitter 2PT: pressure -
2PT, outlet pressure, supply pressure, not used.
Not Used
As Listed
40
2PT Span
Enter value equal to system pressure span
100
0 - 999
41
High 2PT Press.
Enter value of the 2PT pressure above which an alarm will
be set
125
0 - SPAN
42
High 2PT PR. TMR.
Enter in seconds (0 - 60) value of proof timer, ‘0’ disables
this function
20
0 - 60
➀ The top line of each display is stationary while the changeable value, if any, is flashing. The bottom line scrolls from right to left continuously. To scroll from dis-
play continuously press either arrow. At any display the data may be changed by pressing enter, pressing the key or keys to change data, and pressing ENTER
again. If a value to be entered is out of range the following is displayed:
Top Line – value out of range Bottom Line – X1 < = Value < = X2 With X1 being the maximum value and X2 the maximum value of the range