Bell & Gossett S12596B Technologic 350 Pump Controller User Manual

Page 10

background image

10

Default

Allowable

Field

Line #

DISPLAY

Value

Range

Value

21

Destaging PSI
Enter pressure to destage in PSI mode after entering system

0

0 -System

pressure span

Span

22

Forced Destg Tmr.
Enter in minutes (0 - 99) value of a timer after which the
pump will be forced to de-stage; ‘0’ disables this function

60

0 - 99

23

GPM Xmiter Span
Enter value equal to GPM transmitter calibration

0

0 - 30,000

24

2nd Stage Proof
2nd pump stage proof time in seconds

2

1 - 999

25

3rd Stage Proof
3rd pump stage proof time in seconds

2

1 - 999

26

Display Watts
Use up/down keys to enter yes or no

Yes

Y/N

27

Three phase Watts
Use up/down keys to enter yes or no,
YES = three phase, NO = single phase

Yes

Y/N

28

Display AMPs
Use up/down keys to enter yes or no

Yes

Y/N

29

Display GPM
Use up/down keys to enter yes or no

No

Y/N

30

1PT Display Variable
Use the up/down keys to select the variable name for
the signal originating from pressure transmitter 1PT:
pressure - 1PT, inlet pressure, return pressure, not used.

Not Used

As Listed

31

1PT Span
Enter value equal to pressure span

100

0 - 999

32

High 1PT Press.
Enter value of the high pressure above which an alarm
will be set

0

0 - 100

33

High 1PT Pr. TMR.
Enter in seconds (0 - 999) value of high pressure proof timer,
‘0’ disables this function

0

0 - 999

34

High 1PT Reset
Enter value of the high reset pressure

0

0 - 100

35

Low 1PT Press.
Enter value of the low pressure below which an alarm will
be set

5

0 - 100

36

Low 1PT Pr. TMR.
Enter in seconds (0 - 999) value of low pressure proof timer;
‘0’ disables this function

20

0 - 999

37

Low 1PT Reset
Enter value of the low reset pressure

10

0 - 100

38

Low 1PT Auto RST
To change the low reset, use UP/DOWN key to enter yes or no

Yes

Y/N

39

2PT Display Variable
Use the up/down keys to select the variable name for the
signal originating from pressure transmitter 2PT: pressure -
2PT, outlet pressure, supply pressure, not used.

Not Used

As Listed

40

2PT Span
Enter value equal to system pressure span

100

0 - 999

41

High 2PT Press.
Enter value of the 2PT pressure above which an alarm will
be set

125

0 - SPAN

42

High 2PT PR. TMR.
Enter in seconds (0 - 60) value of proof timer, ‘0’ disables
this function

20

0 - 60

➀ The top line of each display is stationary while the changeable value, if any, is flashing. The bottom line scrolls from right to left continuously. To scroll from dis-
play continuously press either arrow. At any display the data may be changed by pressing enter, pressing the key or keys to change data, and pressing ENTER
again. If a value to be entered is out of range the following is displayed:
Top Line – value out of range Bottom Line – X1 < = Value < = X2 With X1 being the maximum value and X2 the maximum value of the range