Xylem iCE3 GPRS Variant User Manual
Page 18

GPRS iCE
3
, V1.30 User Guide
14
iQuest (NZ) Ltd - PO Box 15169, Hamilton, New Zealand Tel: +64 7 857 0810 Fax: +64 7 857 0811 Email: [email protected]
AT^IDTO
Data Forwarding Time Out
Description:
Defines the data gap time (in milliseconds x10) after which the iCE
3
will forward the data
packet to the remote destination. This mode should be used for binary data packets as used
by iQuest products and Campbell Scientific dataloggers.
Default:
20 (200ms)
Notes:
Range is 0-255 (0 -> 2.55 seconds). If this parameter is set to zero, then data will not be
forwarded unless a forwarding character is defined using the AT^IDFC command.
Mode
Command
Responses
Read
AT^IDTO?
^IDTO: 0
OK
Write
AT^IDTO=20
OK OR ERROR
Help
AT^IDTO=?
^IDTO: (0-255)
OK
6.3.7 AT^IGOL
Go On-Line
Description:
Manually initiates connection to the GPRS network. Normally used after a command mode
session where parameters have been viewed or edited and reconnection is required.
Default:
N/A
Notes:
This command is write only.
Mode
Command
Response
Write
AT^IGOL
Connecting…
OK
6.3.8 AT^IHDT
Host Device Type
Description:
Defines the type of device that is connected to the host (RS232) port. Refer to Section 4.2
for details on how each of these device types work and Section 7 for cable information for each.
Default:
0 (Normal)
Notes:
Range is 0-2 (0=Standard, 1=CSI datalogger, 2=Unidata datalogger)
Mode
Command
Responses
Read
AT^IHDT?
^IHDT: 0
OK
Write
AT^IHDT=0
OK OR ERROR
Help
AT^IHDT=?
^IHDT: (0-2)
OK