Is it guaranteed that the PROFIBUS master has consistent access
to the 16 byte sensor data structure?
Note for Siemens PLC with programming language STEP7:
The following commands have to be used for consistent access:
– SFC15 (for writing)
– SFC14 (for reading)
After commissioning:
Do all devices signal error-free behavior?
3.6
Sensor administration under PROFIBUS
Preparation of the IQ S
ENSOR
N
ET
for communication with the
PROFIBUS may require, e.g. the following:
Creating an IQ S
ENSOR
N
ET
system with specific assignment of
sensor numbers to sensors (see section 3.6.1)
Creating several IQ S
ENSOR
N
ET
systems with the identical
assignment of sensor numbers to sensors (see section 3.6.2)
Changing the order of the sensors in an already installed system
3.6.1
Creating the assignment of sensor numbers
You want to install an IQ S
ENSOR
N
ET
system and, at the same time, to
create a specific sequence of sensor number assignments to the
sensors.
1
Carry out a system start without any sensors (see System
operating manual, chapter Installation).
2
Connect the sensors to the system in the required order. For
each sensor, wait until the sensor is recognized by the system
(see System operating manual, chapter Installation).