• To prevent serious burns, the

internal pressure of the regulator

must be 0 psi (0 bar) before

servicing.

• Connect a pipe to the blow

down valve in such a way as to

prevent exposure and injury from

discharge.

Failure to follow this caution will

cause personal injury.

TROUBLESHOOTING

We recommend replacing the Series 754

Regulator when parts no longer operate

properly. A new regulator is more economical
than repairing or replacing individual parts, and it will
provide greater reliability.

Problem:

1.

Inadequate outlet pressure.

a.

Cause: The regulator is not adjusted properly.

Solution: Loosen the locknut on the adjusting

screw and turn it counterclockwise.

b.

Cause: Dirt in the strainer.

Solution: Open the Y-strainer’s blow down gate

valve and allow full steam pressure to
flow for two minutes.

c.

Cause: Steam supply pressure is low.

Solution: Correct boiler steam pressure

problem.

d.

Cause: Dirt under the seat, or the seat is

worn.

Solution: Disassemble regulator and inspect,

replace if necessary.

MAINTENANCE

SCHEDULE:

PROCEDURE:

Initially, every 2-3 days after start-up until system

is clean.

Every 6 months thereafter.

1. Inspect joints for leaks. Stop all leaks by tightening

bolts.

2. Clean strainers by opening the

Y-strainer’s

blow down gate valve

and allowing full steam

pressure to flow out for (2) two minutes. Then,
close the valve.

3. If steam escapes from the vent hole in the spring

housing area, replace the diaphragms.

!

WARNING