Hoffman specialty, Maximum operating pressure 1, Psig. maximum pressure 10 psig

background image

Maximum operating pressure 1

1

2

psig.

Maximum pressure 10 psig.

1A
1/8" NPT
Connection

1B
1/4" NPT
Connection

MAINTENANCE
INSPECT ANNUALLY:
This vent allows air to
escape from the radiator as the steam pushes in.
A cold upper part of the radiator may indicate the
vent is plugged with scale or is malfunctioning.
Vapor or slight moisture from the vent is normal.
Steam continuously passing through the vent
indicates a malfunction. Replace the vent as
needed or every 10 years.