INSTALLATION

Steam

Supply

Globe Valve Recommended

For Throttling Purposes

Optional By-Pass Line

Series 754

Pressure

Reducing

Regulator

By-Pass

Inlet

Relief
Valve

Y Strainer

Y Strainer

F&T

Trap

Gate

Valve

Gate

Valve

C

P

A

F

H

G

R

D

E

F

Pipe Opening

G

J

1. Determine where to install the regulator, based

on the following requirements:

a. The regulator must be installed where it can

be accessed for adjustment and repair.

2. Install the following ahead of where the regulator

will be installed.

a. A drip trap (A), Y-strainer (P) and gate valve

(R). This insures dry steam.

b. A gate valve (C), Y-strainer (H), pressure

gauge (D), and union (E) in the inlet piping
(F).

c. Install a gate valve (G) in the Y-strainer (H)

for blow down.

3 a. Cap off the outlet pipe (J).

b. Open the Y-strainer’s blow down gate valve (G).

c. Slowly turn steam on with full pressure for five (5)

minutes to blow down the inlet pipe (F).

d. Turn off steam and allow pipe to cool.

e. Remove cap from the outlet pipe (J) and

close the Y-strainer’s blow down gate valve (G).

• To prevent serious burns, the internal pressure of the regulator must be 0 psi (0 bar)

before servicing.

• Connect a pipe to the blow down valve in such a way as to prevent exposure and injury

from discharge.

Failure to follow this caution will cause personal injury.

!

WARNING