beautypg.com

Bell & Gossett A01500I Pressurized Expansion Tanks (ASME) User Manual

Pressurized expansion tanks (asme), Instruction manual

background image

SAFETY

INSTRUCTIONS

This safety alert symbol will be used in this manual to draw attention to
safety related instructions. When used, the safety alert symbol means

ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED!

FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A

SAFETY HAZARD.

DESCRIPTION

Precharged Expansion Tanks contain either a bladder or a diaphragm
to separate the air charge from the system water. Tanks are designed
to absorb the expansion forces of heating/cooling system water while
maintaining proper system pressurization under varying operating
conditions.

NOT FOR USE IN DOMESTIC

(POTABLE) WATER SYSTEMS

DANGER: Series “B”, “D”, & “B-LA” are for use in closed loop
systems only. Domestic, potable or fresh water can cause serious
corrosion in a tank. This can result in leakage and a potential
explosion. Do not use for domestic, potable or fresh water. Failure
to follow this instruction will result in serious personal injury or
death and property damage.

OPERATIONAL LIMITS

Maximum Operating Pressure: 125 psi (or as stamped on nameplate)
Maximum Operating Temperature: 240ºF
Minimum Operating Temperature: 35°F (non-glycol application)

18°F (glycol application)

Pressurized Expansion Tanks (ASME)

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

Series "D"

Series "B-LA"

Series "B"

WARNING LABEL PART NO. 9015-463 INSTALLED IN THIS

LOCATION. IF MISSING, IT MUST BE REPLACED.

WARNING: Explosion Hazard
Failure to follow instructions in the accompanying product

manual can cause rupture or explosion, possibly causing serious or
fatal injury, leaking or flooding and/or property damage.

WARNING: Carefully read the Instruction Manual to avoid
serious personal injury and property hazards and to ensure

safe use and proper care of this product.

INSTRUCTION MANUAL

A01500I