Operating instructions, Service instruction – Bell & Gossett A07258B Check-Trol Flange User Manual
Page 2

TABLE 1
Pressure – Temperature Ratings
Melting Range
Working Temperature
Maximum Working Gauge Pressure
Joining
Degrees
Degrees
Size
1
⁄
8
" – 1"
Size 1
1
⁄
4
" – 2"
Size 2
1
⁄
2
" – 4"
Material
°F
°C
°F
°C
psi
kPa
psi
kPa
psi
kPa
95-tin-antimony
0/+100
-18/+38
500*
3500*
400*
2800*
300*
2100*
solder
450/464
230/240
0/+150
-18/+66
400*
2800*
350*
2400*
275*
2000*
ASTM B32 alloy
0/+200
-18/+93
300*
2100*
250*
1700*
200
1400
grade 95TA
0/+250
-18/+121
200
1400
175
1200
150
1050
Note: Above stated limits are not imposed by the valve, but by the strength of the soldering joint according to ASME B16.22.
*Soldered copper tube joints have been tested at 230 psi (1600 kPa) in accordance with ISO 2016.
.
.
d) While soldering, it is important to use a properly sized torch with a
sharp pointed flame so that the solder end is heated fully and quickly.
Apply heat so that the flame is directed on the cup area but away
from the valve body. Although soft 50/50 solder is easier to use,
these valves can also be successfully soldered with 95-5, however
caution must be used to prevent damage (see table 1.) Cool the
valve body before soldering the second end.
e) Check the soldered connections for leaks.
OPERATING INSTRUCTIONS
To isolate the circulator from the system, turn the handle of both isola-
tion valves clockwise 90° to close the valve. Remove circulator for
repair/replacement.
IMPORTANT: Relieve pressure from the circulator by slowly loosening
the bolts allowing the water to slowly drain from the pump body. Refer
to the circulator instruction manual when reinstalling a circulator. After
a pump is reinstalled, turn the handle of both isolation valves counter-
clockwise 90° to open the valves for normal operation.
SERVICE INSTRUCTION
There is no service required for the Isolation or Check-Trol™ flanges.
CAUTION: Heat associated with the use of silver solder may
damage valve and void the warranty. Do not use silver sol-
der. Failure to follow these instructions could result in property dam-
age and/or moderate personal injury.
CAUTION: Corrosion or leakage of the valves can cause
damage or injury. Periodically inspect the valves for signs of
leakage or corrosion. If corrosion or leakage is noted, the valves must
be replaced. Failure to follow these instructions could result in prop-
erty damage and/or moderate personal injury.
DISCHARGE SIDE
USE CHECK-TROL
TM
FLANGE
SUCTION SIDE
USE ISOLATION FLANGE
STANDARD
PIPING
VALVE OPEN
NORMAL OPERATION
VALVE CLOSED
FOR SERVICING
Xylem Inc.
8200 N. Austin Avenue
Morton Grove, Illinois 60053
Phone: (847) 966-3700
Fax: (847) 965-8379
www.xyleminc.com/brands/bellgossett
Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.
© 2012 Xylem Inc. A07258B May 2012