Fitting (cont.)

80°

80°

H

I

K

L

> h

h

Selecting the installation location

H Surveillance cone: entire workplace; not on window sur-

faces.

I Avoid exposure to direct light.
K Avoid drafts (e.g. from ventilators or fans).
L Installation distance = min. installation height

Adjusting the detection area

Tilt the motion sensor up to 30° in the required direction.

Appendix

Technical data

Combined control and

supply connection

4-pin modular connection (4p4c)
1: Supply voltage

2: Light measurement value

3: Motion signal

4: Signal ground
Length 2.1 m

Maximum total length

of signal line (incl. all

connections to the

control units)

See control unit

Insulation

Basic insulation as per IEC 664

Dimensions

(L x W x H)

48 x 29 x 24.5 mm

Light sensor detection

area

20 - 600 lx (measured at sensor),

opening angle approx. 90°

Motion detection area

Conical, opening angle approx. 80°

Installation height

2 - 4 m

The CE requirements to EN 60928 are fulfilled.

The EMC requirements to EN 61547 are fulfilled.