Installation (cont.)
Technical data
Operating voltage
100-240 VAC / 50-60 Hz
(DC operation permissible)
Supply
connection
L, N (PE not required)
Control
connections
1…10 V control signal as per
EN 60929 Annex E2, a maximum of 10
electronic ballasts can be connected
Pushbutton input
Potential-free make contact, max. line
length 50 m
Sensor connection
Max. 2 sensors, max. line length
25 m
Pin assignment:
1: Supply voltage (+ 3.3 V)
2: Light measurement
3: Motion signal
4: Ground
Max. load contact load
capacity L’
5 A resistive load
Max. number of ECGs: 10 (depends
on the ECG type to be connected)
Fuse
External 16 A
Power consumption
Operation: 1 W
Standby: < 0.5 W
Ambient temperature
0 °C … +50 °C
Adjustable light value
20-600 lux (measured at sensor)
Protection type
IP 20
Protection class
II
Dimensions
(L x W x H)
118 x 30 x 21 mm
Hole distance for
mounting
110 mm
The CE requirements to EN 60928 are fulfilled. The EMC requi-
rements to EN 61547 are fulfilled.
Conformity with the relevant EU directives is
confirmed by the CE symbol.
Connecting the control unit
Left: Individual operation with max. 2 sensors
Right: Networked operation with up to 4 DIM MULTIeco control
units and central presence detection
H Sensor
J Pushbutton
K Lamp
L Y-Connector
M Y-Connector Screw
N To luminaire group 1
O To luminaire group 2
1 2 3 4
1 2 3 4
L
N
J
N
L
N
Sensor
DIM MULTIeco
J
O
L
N
Sensor
DIM MULTIeco
H
M
L
H
L
J
K
L
N
L‘
1…10V+
1…10V -
1…10 V+
1…10 V -
~
~
1…10 V+
1…10 V -
~
~
Sensor
DIM MULTIeco
QTi DIM EVG
QTi DIM EVG
N
PE
K
H
Appendix
1 2 3 4
Pin