Installation (cont.)
F
G
I
H
E
100°
100°
2,5 m
3,5 m
3
m
Vcc LS 0V
NC
PD
NC
OSRAM
DALI LS/PD
BASIC
Vcc
(+)
(-)
0V
LS
PD
58,5
42
70
,5
Conformity with the relevant EU directives is
confirmed by the CE symbol.
Appendix
Technical data
Operating voltage
Nominal 10 V DC
(8 – 20 V DC)
Current consumption
Max. 3 mA DC
Maximum total line
length
100 m
Line connection
Screw terminals for single-wire
or fine-wire conductors with 0.3 –
1.5 mm²
Operating temperature
0 °C … +50 °C
Operating range
Up to 400 lx measured at sensor
Detection area
Conical, opening angle approx.
100°
Pollution severity
2 (dry, not conductive, as per
IEC 664)
Dimensions
(L x W x H)
58.5 x 70.5 x 42 mm
Weight
Approx. 70 g
Protection type
IP 20
Protection class
II
Selecting the installation location
E Optimal mounting height: 2.5 – 3 m. As the mounting height
increases, the detection area increases and sensitivity is
reduced.
F Monitoring cone: entire workplace; not on window surfaces
G Avoid exposure to direct light.
H Place devices that radiate heat outside of the monitoring
cone.
I Avoid drafts (e.g. from ventilators).
Dimensioned drawing
Connecting the sensor
K Light measurement value
L Motion signal