beautypg.com

3 operation, settings, 4 technical data – OSRAM DALIeco LS User Manual

Page 9

background image

9

3 Operation,

settings

Use of the sensor and confi guration in the system

separate manual for the control unit used.

3.1 Setting the detection range for presence detection

In order to use the presence detection in a targeted way, the detection range of the sensor can/

must be set independently of the spatial conditions

7

.

1.

Remove/insert or rotate one or both shutters where necessary.

2.

By changing the shutter position, you can infl uence the detection range of the sensor direc-

tionally in order to prevent undesired presence detection.

3.

For a quick test of the effectiveness of the settings, use the test function of the remote

control used

separate manual for the control unit used.

3.2 Sensor button

3a

This button (2) executes different functions depending on the duration of activation.

1.

Press the sensor button (SP) in order to switch the IR reception of the remote controls on

(sensor LED fl ashes red for 3 seconds) or off (sensor LED illuminated red for 3 seconds)

2.

Press the sensor button (VLP) in order to start Auto Setup and thereby calibration.

After a 3-minute calibration, the light fl ashes and the automatic lighting control is started.

Functional description of Auto Setup

separate manual for the control unit used.

4 Technical

data

Cable connection

4p4c, max. total cable length 25 m

Ambient temperature

-20 °C to +50 °C (operation)

Max. cable length, sensor

25 m, ensure contact assignment 1:1
for extension/shortening

Working range, light sensor

20 - 800 lux (directly on the sensor)

Protection class

IP20

CE conformity

EMC acc. to EN 61547; low voltage acc. to EN 60928

Installation height

max. 5.0 m

Detection range

max. Ø 7.0 m

Detection angle

40° - 90°

Detection range adjustable via shutter (min. 40° - max. 90°)

Installation height 2.0 m
Installation height

2.5 m

Installation height

3.0 m

Installation height

3.5 m

Max. installation height 5.0 m

Detection range

Ø 1.5 m - 4.0 m

Detection range

Ø 1.8 m - 5.0 m

Detection range

Ø 2.0 m - 6.0 m

Detection range

Ø 2.5 m - 7.0 m

Max. detection range